Elimination of transformer inrush currents by controlled switching -: Part I:: Theoretical considerations

被引:184
作者
Brunke, JH [1 ]
Fröhlich, KJ
机构
[1] Bonneville Power Adm, Vancouver, WA USA
[2] Swiss Fed Inst Technol, Zurich, Switzerland
关键词
controlled switching; inrush current; residual flux; transformer switching;
D O I
10.1109/61.915495
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Transformer inrush currents are high-magnitude, harmonic-rich currents generated when transformer cores are driven into saturation during energization. These currents have undesirable effects, including potential damage or loss-of-life to the transformer, protective relay misoperation, and reduced power quality on the system, Controlled transformer snitching can potentially eliminate these transients if residual core and core flux transients are taken into account in the closing algorithm, This paper explores the theoretical considerations of core flux transients. Based on these studies algorithms were developed which allow controlled energization of most transformers without inrush current.
引用
收藏
页码:276 / 280
页数:5
相关论文
共 5 条
[1]  
BRUNKE JH, 1998, THESIS ETH ZURICH
[2]  
Colombo E., 1984, Electra, P35
[3]  
*EMTP, 1980, EL TRANS PROGR RUL B, P227
[4]  
HOLMGREN R, 1968, CIGRE PARIS, P1
[5]  
MORAW G, 1988, CIGRE, P1