Comparative analysis between ROCOF and vector surge relays for distributed generation applications

被引:249
作者
Freitas, W [1 ]
Xu, WS
Affonso, CM
Huang, ZY
机构
[1] Univ Estadual Campinas, Dept Elect Energy, BR-13081970 Campinas, SP, Brazil
[2] Univ Alberta, Dept Elect & Comp Engn, Edmonton, AB T6G 2V4, Canada
[3] Pacific NW Natl Lab, Energy Sci & Technol Div, Richland, WA 99352 USA
基金
巴西圣保罗研究基金会;
关键词
distributed generation; islanding detection; rate of change of frequency (ROCOF) relays; vector-surge (VS) relays;
D O I
10.1109/TPWRD.2004.834869
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
This paper presents a comprehensive comparative analysis between rate-of-change-of-frequency (ROCOF) and vector-surge (VS) relays for distributed generation islanding detection. The analysis is based, on the concepts of detection-time versus active power-imbalance curves and critical active power imbalance. Such curves are obtained through dynamic simulations. The performance of these devices considering different scenarios is determined and compared. Factors such as voltage-dependent loads, generator inertia constant, and multidistributed generator systems are analyzed. False operation of these relays due to faults in adjacent feeders is also addressed. Results show that ROCOF relays are more reliable to detect islanding than vector surge relays when the active power imbalance in the islanded system is small. However, ROCOF relays are more susceptible to false operation than VS relays.
引用
收藏
页码:1315 / 1324
页数:10
相关论文
共 8 条
[1]  
CIRED CIRED Working Group 4, 1999, DISP GEN
[2]  
ClGRE, 1999, IMP INCR CONTR DISP
[3]  
*EL ASS, 1991, G591 EL ASS
[4]  
*IEEE, 2003, STAND COORD COMM 21
[5]  
Jenkins N, 2000, EMBEDDED GENERATION
[6]  
Kundur P., 1994, POWER SYSTEM STABILI
[7]  
PRICE WW, 1993, IEEE T POWER SYST, V8, P472
[8]  
Walling RA, 2002, 2002 IEEE POWER ENGINEERING SOCIETY SUMMER MEETING, VOLS 1-3, CONFERENCE PROCEEDINGS, P92, DOI 10.1109/PESS.2002.1043183