This paper considers the design of cooling systems in the context of piping costs, exchanger costs, pumping costs and its hydraulic and thermal performance. A methodology for designing coolers in the context of both process needs and cooling water system behaviour is introduced. It is recognised that cooling systems need to be flexible. One way of ensuring this is to design a system for the most demanding load and then use bypasses to control performance under reduced load. The hydraulic modelling is based on new formulations of flow resistance for pipes, pipe fittings and equipment items. By using volumetric flow rate rather than velocity as the prime variable it becomes possible to construct hydraulic models for cooling water systems quickly. These calculations then provide predictions of water flows to the individual heat exchangers in the cooling water network Knowledge of these flows is fundamental to both the design of new coolers and the prediction of the thermal performance of exchangers of known geometry. Previous studies have ignored this aspect of design. (C) 2011 Elsevier Ltd. All rights reserved.
引用
收藏
页码:4646 / 4653
页数:8
相关论文
共 21 条
[1]  
Bernier M.A., 1994, ASHRAE T, V100, P114
[2]   Minimization of operational costs in cooling water systems [J].
Castro, MM ;
Song, TW ;
Pinto, JM .
CHEMICAL ENGINEERING RESEARCH & DESIGN, 2000, 78 (A2) :192-201
[3]   A modified analysis of counter flow wet cooling towers [J].
ElDessouky, HTA ;
AlHaddad, A ;
AlJuwayhel, F .
JOURNAL OF HEAT TRANSFER-TRANSACTIONS OF THE ASME, 1997, 119 (03) :617-626
[4]   Experimental study on the performance of mechanical cooling tower with two types of film packing [J].
Gharagheizi, Farhad ;
Hayati, Reza ;
Fatemi, Shohreh .
ENERGY CONVERSION AND MANAGEMENT, 2007, 48 (01) :277-280
[5]  
Hodge B.K., 1999, ANAL DESIGN ENERGY S
[6]   Design of Cooling Towers by the Effectiveness-NTU Method [J].
Jaber, H. ;
Webb, R. L. .
JOURNAL OF HEAT TRANSFER-TRANSACTIONS OF THE ASME, 1989, 111 (1-4) :837-843
[7]  
Jameel-Ur-Rehman K, 2004, INT J REFRIG, V27, P914
[8]  
Kays W.M., 1984, COMPACT HEAT EXCHANG, V3rd
[9]  
Kern D.Q., 1950, PROCESS HEAT TRANSFE
[10]   Performance characteristics of counter flow wet cooling towers [J].
Khan, JUR ;
Yaqub, M ;
Zubair, SM .
ENERGY CONVERSION AND MANAGEMENT, 2003, 44 (13) :2073-2091