Design of WAMS-Based Multiple HVDC Damping Control System

被引:55
作者
Wang Juanjuan [1 ]
Fu Chuang [2 ]
Zhang Yao [1 ]
机构
[1] S China Univ Technol, Coll Elect Engn, Guangzhou, Guangdong, Peoples R China
[2] China Southern Power Grid, Elect Power Res Inst, Guangzhou, Guangdong, Peoples R China
关键词
Multiple HVDC damping controller; Prony method; relative gain array (RGA); residue analysis; WAMS; wide-area signal;
D O I
10.1109/TSG.2011.2118773
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
High voltage direct current (HVDC) links are interties, characterized by good controllability, large adjustable capacity and fast responses, and have inherent advantage in damping interarea oscillations over power system stabilizers (PSS) and flexible alternating current transmission systems (FACTS). In this paper, a systematic and practical means to design the multiple HVDC damping control system, which aims to enhance the damping of certain interarea modes and minimize the interactions between different control loops, is provided. In the proposed procedure, the wide-area feedback signals that have the good observability of target modes are preselected by an index based on residue analysis firstly. Then the interactions between the candidate control loops, in which the setting power reference of the HVDC as the input and the preselected wide-area signals as the output, are investigated by relative gain array (RGA) analysis. According to the RGA results, a suitable input-output pairing for multiple HVDC damping controller is determined. The transfer function residues used in the feedback signal preselection and the RGA calculation are identified by Prony analysis in the transient stability program and electromagnetic transient program respectively. Finally, the damping controller parameters are optimized by time-domain simulations. The application in China Southern Power Grid (CSG) is illustrated as the case study.
引用
收藏
页码:363 / 374
页数:12
相关论文
共 45 条
[1]  
[Anonymous], 1994, POWER SYSTEM STABILI
[3]   A comparative assessment of two techniques for modal identification from power system measurements [J].
Browne, Timothy James ;
Vittal, Vijay ;
Heydt, Gerald Thomas ;
Messina, Arturo Roman .
IEEE TRANSACTIONS ON POWER SYSTEMS, 2008, 23 (03) :1408-1415
[4]   Wide-area measurement-based stabilizing control of power system considering signal transmission delay [J].
Chaudhuri, B ;
Majumder, R ;
Pal, BC .
IEEE TRANSACTIONS ON POWER SYSTEMS, 2004, 19 (04) :1971-1979
[5]   AN ADAPTIVE POWER-SYSTEM STABILIZER BASED ON THE SELF-OPTIMIZING POLE SHIFTING CONTROL STRATEGY [J].
CHEN, GP ;
MALIK, OP ;
HOPE, GS ;
QIN, YH ;
XU, GY .
IEEE TRANSACTIONS ON ENERGY CONVERSION, 1993, 8 (04) :639-645
[6]   Robust pole placement in LMI regions [J].
Chilali, M ;
Gahinet, P ;
Apkarian, P .
IEEE TRANSACTIONS ON AUTOMATIC CONTROL, 1999, 44 (12) :2257-2270
[7]   Synchronized Phasor Measurement Applications in Power Systems [J].
De La Ree, Jaime ;
Centeno, Virgilio ;
Thorp, James S. ;
Phadke, A. G. .
IEEE TRANSACTIONS ON SMART GRID, 2010, 1 (01) :20-27
[8]   CONCEPTS OF SYNCHRONOUS MACHINE STABILITY AS AFFECTED BY EXCITATION CONTROL [J].
DEMELLO, FP ;
CONCORDIA, C .
IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1969, PA88 (04) :316-+
[9]   Wide-Area Measurements-Based Two-Level Control Design Considering Signal Transmission Delay [J].
Dotta, Daniel ;
Silva, Aguinaldo S. e ;
Decker, Ildemar C. .
IEEE TRANSACTIONS ON POWER SYSTEMS, 2009, 24 (01) :208-216
[10]   Reduced-order method for computing critical eigenvalues in ultra large-scale power systems [J].
Fang, W. ;
Wei, P. ;
Du, Z. .
IET GENERATION TRANSMISSION & DISTRIBUTION, 2010, 4 (07) :836-845