A general methodology for energy comparison of intermediate configurations in two-stage vapour compression refrigeration systems

被引:53
作者
Torrella, E. [2 ]
Larumbe, J. A. [2 ]
Cabello, R. [1 ]
Llopis, R. [1 ]
Sanchez, D. [1 ]
机构
[1] Jaume I Univ, Dept Mech Engn & Construct, E-12071 Castellon de La Plana, Spain
[2] Univ Politecn Valencia, Dept Appl Thermodynam, E-46022 Valencia, Spain
关键词
Two-stage refrigerating cycle; Vapour compression; Inter-stage pressure; COMPOUND COMPRESSOR; CYCLE; OPTIMIZATION;
D O I
10.1016/j.energy.2011.04.034
中图分类号
O414.1 [热力学];
学科分类号
摘要
The aim of the present paper is to describe a general methodology suitable for analysing any intermediate configuration considered in staged vapour compression refrigeration cycles. This general methodology only depends on two basic parameters related to the subcooling and desuperheating obtained in the inter-stage system. A COP expression based on the two basic parameters was obtained from the general configuration. By means of its particularization to seven common configurations, it was then possible to make an energy comparison of the various configurations working with two fluids appropriated for the low temperature domain such as ammonia and R-404A. (C) 2011 Elsevier Ltd. All rights reserved.
引用
收藏
页码:4119 / 4124
页数:6
相关论文
共 15 条
[1]   Optimization of two-stage transcritical carbon dioxide heat pump cycles [J].
Agrawal, Neeraj ;
Bhattacharyya, Souvik ;
Sarkar, J. .
INTERNATIONAL JOURNAL OF THERMAL SCIENCES, 2007, 46 (02) :180-187
[2]   Studies on a two-stage transcritical carbon dioxide heat pump cycle with flash intercooling [J].
Agrawal, Neeraj ;
Bhattacharyya, Souvik .
APPLIED THERMAL ENGINEERING, 2007, 27 (2-3) :299-305
[3]  
[Anonymous], 1995, 5606 NAT I SCI TECHN
[4]  
[Anonymous], HVAC RES
[5]  
[Anonymous], 1959, ALLGEMEINE WARMETECH
[6]  
[Anonymous], INT J EXERGY
[7]  
[Anonymous], P 9 INT C REFR PAR F
[8]  
ARORA CP, 1971, P 13 INT C REFR PAR, P693
[9]   Two-stage transcritical carbon dioxide cycle optimisation: A theoretical and experimental analysis [J].
Cavallini, A ;
Cecchinato, L ;
Corradi, M ;
Fornasieri, E ;
Zilio, C .
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2005, 28 (08) :1274-1283
[10]  
CELIK A, 2004, PERFORMANCE 2 STAGE