Evaluation of a turbine driven CCHP system for large office buildings under different operating strategies

被引:179
作者
Mago, Pedro J. [1 ]
Hueffed, Anna K. [1 ]
机构
[1] Mississippi State Univ, Dept Mech Engn, Mississippi State, MS 39762 USA
关键词
CCHP; Primary energy reduction; Carbon dioxide emissions; Trigeneration; Carbon credits; CHP SYSTEM; ENERGY; POWER; OPTIMIZATION; PERFORMANCE; DESIGN;
D O I
10.1016/j.enbuild.2010.04.005
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
Combined cooling, heating, and power (CCHP) systems use waste heat from on-site electricity generation to meet the thermal demand of the facility. This paper models a CCHP system for a large office building and examines its primary energy consumption (PEC), operational costs, and carbon dioxide emissions (CDE) with respect to a reference building using conventional technologies. The prime mover used in this investigation is a load share turbine, and the CCHP system is evaluated under three different operation strategies: following the electric demand of the facility, following the thermal demand of the facility, and following a seasonal strategy. For the various strategies, the percentages of total carbon dioxide emissions by source are presented. This paper explores the use of carbon credits to show how the reduction in carbon dioxide emissions that is possible from the CCHP system could translate into economic benefits. In addition, the capital costs available for the CCHP system are determined using the simple payback period. Results indicate that for the evaluated office building located in Chicago the CCHP operation reduces the operational cost, PEC, and CDE from the reference building by an average of 2.6%, 12.1%, and 40.6%, respectively, for all the different operational strategies. (C) 2010 Elsevier B.V. All rights reserved.
引用
收藏
页码:1628 / 1636
页数:9
相关论文
共 22 条
  • [1] *ASHRAE, 2008, SYST EQ HDB
  • [2] ASHRAE, 2007, 901 ANSIASHRAEIESNA
  • [3] A new approach to exergoeconomic analysis and design of variable demand energy systems
    Cardona, E
    Piacentino, A
    [J]. ENERGY, 2006, 31 (04) : 490 - 515
  • [4] A validation methodology for a combined heating cooling and power (CHCP) pilot plant
    Cardona, E
    Piacentino, A
    [J]. JOURNAL OF ENERGY RESOURCES TECHNOLOGY-TRANSACTIONS OF THE ASME, 2004, 126 (04): : 285 - 292
  • [5] Cost-optimized real-time operation of CHP systems
    Cho, Heejin
    Luck, Rogelio
    Eksioglu, Sandra D.
    Chamra, Louay M.
    [J]. ENERGY AND BUILDINGS, 2009, 41 (04) : 445 - 451
  • [6] Experimentation on a cogenerative system based on a microturbine
    Colombo, Luigi P. M.
    Armanasco, Fabio
    Perego, Omar
    [J]. APPLIED THERMAL ENGINEERING, 2007, 27 (04) : 705 - 711
  • [7] *DOE, 2008, COMM BUILD BENCHM MO
  • [8] Energy, economic and environmental (3E) analysis of a micro gas turbine employed for on-site combined heat and power production
    Ehyaei, M. A.
    Mozafari, A.
    [J]. ENERGY AND BUILDINGS, 2010, 42 (02) : 259 - 264
  • [9] EnergyPlus, EN SIM SOFTW
  • [10] Cooling, heating, and power energy performance for system feasibility
    Fumo, N.
    Mago, P. J.
    Chamra, L. M.
    [J]. PROCEEDINGS OF THE INSTITUTION OF MECHANICAL ENGINEERS PART A-JOURNAL OF POWER AND ENERGY, 2008, 222 (A4) : 347 - 354