superconducting fault current limiters;
(SCFCLs);
trigger current level;
recovery time;
fault time;
D O I:
10.1109/77.920267
中图分类号:
TM [电工技术];
TN [电子技术、通信技术];
学科分类号:
0808 [电气工程];
0809 [电子科学与技术];
摘要:
The recovery time of a transformer type SCFGL (Superconducting Fault Current Limiter) with adjustable trigger current level, is studied experimentally. The recovery time is defined as the required time of zero current period of SCFCL for recovery from its current limiting mode to its waiting mode. A trial SCFCL, which was designed and made, Is tested to measure the recovery time with various fault time. The experimental results show that the recovery time depends on the fault time. When the fault time is longer than 200 ms, the recovery time becomes shorter and approaches a certain value (a few ten ms) as the fault time is longer.