A multi-phase genetic algorithm for the efficient management of multi-chiller systems

被引:61
作者
Beghi, Alessandro [1 ]
Cecchinato, Luca [2 ]
Rampazzo, Mirco [1 ]
机构
[1] Univ Padua, Dipartimento Ingn Informaz, I-35131 Padua, Italy
[2] Univ Padua, Dipartimento Fis Tecn, I-35131 Padua, Italy
关键词
Multiple-chiller; Optimal Chiller Loading; Optimal Chiller Sequencing; Genetic algorithm;
D O I
10.1016/j.enconman.2010.10.028
中图分类号
O414.1 [热力学];
学科分类号
摘要
In HVAC plants of medium-high cooling capacity, multiple-chiller systems are often employed. In such systems, chillers are independent of each other to provide standby capacity, operational flexibility, and less disruption maintenance. However, the problem of efficiently managing multiple-chiller systems is complex in many respects. In particular, the electrical energy consumption in the chiller plant markedly increases if the chillers are managed improperly, therefore significant energy savings can be achieved by optimizing the chiller operations of HVAC systems. In this paper an unified method for Multi-Chiller Management optimization is presented, that deals simultaneously with the Optimal Chiller Loading and Optimal Chiller Sequencing problems. The main objective is that of reducing both power consumption and operative costs. The approach is based on a cooling load estimation algorithm, and the optimization step is performed by means of a multi-phase genetic algorithm, that provides an efficient and suitable approach to solve this kind of complex multi-objective optimization problem. The performance of the algorithm is evaluated by resorting to a dynamic simulation environment developed in Matlab/Simulink (TM), where the plant dynamics are accurately described. It is shown that the proposed algorithm gives superior performance with respect to standard approaches, in terms of both energy performance and load profile tracking. (C) 2010 Elsevier Ltd. All rights reserved.
引用
收藏
页码:1650 / 1661
页数:12
相关论文
共 20 条
[1]  
Adnot J., 2003, ENERGY EFFICIENCY CE
[2]   Advanced control systems for single compressor chiller units [J].
Albieri, Michele ;
Beghi, Alessandro ;
Bodo, Cristian ;
Cecchinato, Luca .
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2009, 32 (05) :1068-1076
[3]  
[Anonymous], 1979, LINEAR SYSTEMS
[4]  
[Anonymous], ASHRAE T
[5]  
ASHRAE, 2007, ASHRAE HDB HVAC APPL, P4136
[6]  
ASHRAE, 2008, ASHRAE HDB HVAC SYST
[7]  
Atanasiu B, 2006, ELECT CONSUMPTION EF
[8]  
Bettanini E., 2003, 8 INT IBPSA C EINDH
[9]   Optimal chiller sequencing by branch and boun method for saving energy [J].
Chang, YC ;
Lin, FA ;
Lin, CH .
ENERGY CONVERSION AND MANAGEMENT, 2005, 46 (13-14) :2158-2172
[10]   Optimal chiller loading by genetic algorithm for reducing energy consumption [J].
Chang, YC ;
Lin, JK ;
Chuang, MH .
ENERGY AND BUILDINGS, 2005, 37 (02) :147-155