An improved design and rating analyses of counter flow wet cooling towers

被引:67
作者
Khan, JUR [1 ]
Zubair, SM [1 ]
机构
[1] King Fahd Univ Petr & Minerals, Dept Mech Engn, Dhahran 31261, Saudi Arabia
来源
JOURNAL OF HEAT TRANSFER-TRANSACTIONS OF THE ASME | 2001年 / 123卷 / 04期
关键词
cooling towers; direct contact; heat transfer; heat exchangers; modeling;
D O I
10.1115/1.1376395
中图分类号
O414.1 [热力学];
学科分类号
摘要
Cooling towers are one of the largest heat and mass transfer devices that are in common use. In this paper, we present a detail model of counter flow wet cooling towers. The authenticity of the model is checked by experimental data reported in the literature. The values of number of transfer units (NTU) and tower effectiveness (epsilon) obtained from the model were compared with the commonly described models. Appreciable difference in NTU and e values is found if the resistance to heat transfer in the water film and non-unity, of Lewis number is considered in the calculations. The results demonstrate that the errors in calculating the tower effectiveness could be cis much as 15 percent when considering the effect of air-water interface temperature. A procedure for the use of the model in designing and rating analyses of cooling towers is demonstrated through example problems. The limiting performance of the cooling towers; that is effectiveness equal to one, is explained in terms of air-approach temperature. The model is also used for obtaining the maximum possible mass-flow rate ratio of water-to-air, for different operating conditions.
引用
收藏
页码:770 / 778
页数:9
相关论文
共 16 条
[1]  
*ASHRAE, 1983, ASHRAE EQ G12D, pCH3
[2]  
ASHRAE, 1989, ASHRAE Handbook-Fundamentals, VI-P
[3]  
BAKER DR, 1961, T ASME, V83, P339
[4]  
BRAUN JE, 1989, ASHRAE T, V95, P165
[5]   A modified analysis of counter flow wet cooling towers [J].
ElDessouky, HTA ;
AlHaddad, A ;
AlJuwayhel, F .
JOURNAL OF HEAT TRANSFER-TRANSACTIONS OF THE ASME, 1997, 119 (03) :617-626
[6]  
HYLAND R, 1983, ASHRAE J, V25, P64
[7]  
Hyland R. W., 1983, ASHRAE Transactions, V89, P500
[8]   Design of Cooling Towers by the Effectiveness-NTU Method [J].
Jaber, H. ;
Webb, R. L. .
JOURNAL OF HEAT TRANSFER-TRANSACTIONS OF THE ASME, 1989, 111 (1-4) :837-843
[9]  
Kuehn T., 1998, THERMAL ENV ENG
[10]  
Merkel F., 1925, Zeitschrift desvereines Dentscher Ingenieure, V70, P123