Intermittent Fault Location in Distribution Feeders

被引:48
作者
Alamuti, Mohsen Mohammadi [1 ]
Nouri, Hassan [1 ]
Ciric, Rade M. [2 ]
Terzija, Vladimir [3 ]
机构
[1] Univ W England, Bristol BS16 1QY, Avon, England
[2] Univ Belgrade, Belgrade 11000, Serbia
[3] Univ Manchester, Manchester M13 9PL, Lancs, England
基金
英国工程与自然科学研究理事会;
关键词
Arcing fault location; distribution feeder; single end; NUMERICAL ALGORITHM; ARCING FAULT; AUTORECLOSURE; PROTECTION;
D O I
10.1109/TPWRD.2011.2172695
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Due to the utilization of fundamental frequency, current impedance-based fault-location methods are able to locate only permanent and linear faults. The duration of the arc in low- and medium-voltage systems can be as short as a quarter of a cycle. This period, which is normal for intermittent faults, is insufficient for fundamental frequency-based fault-location algorithms. Therefore, available methods are not applicable for an intermittent arcing fault location. In this paper, a novel method is proposed for arcing fault location in radial feeders, utilizing time-based formulation considering the short duration of the faults. The advantage of the proposed method over available methods is its capability for locating faults using fewer samples, which is suitable for arcing faults as well as normal faults in the network. Also, different types of faults are taken into account in the proposed algorithm. The validity of the devised algorithm is studied within the PSCAD-EMTDC environment and the results obtained show good accuracy for arcing faults. The application of the proposed algorithm in real systems is based on the availability of measured voltage and current waveforms at one end of the network and knowledge of cable/line parameters (self and mutual impedances).
引用
收藏
页码:96 / 103
页数:8
相关论文
共 23 条
[1]  
Alamuti M. M., 2009, 44 INT U POW ENG C G
[2]  
[Anonymous], 2008, EUR J SCI RES
[3]  
Charytoniuk W, 2000, IEEE T IND APPL, V36, P1756, DOI 10.1109/28.887231
[4]  
Ece D. G., 1994, 7 MED EL C ANT TURK
[5]   Evaluation of LV and MV arc parameters [J].
Gaudreau, Andre ;
Koch, Bohdan .
IEEE TRANSACTIONS ON POWER DELIVERY, 2008, 23 (01) :487-492
[6]   Intermittent arcing fault on underground low-voltage cables [J].
Hamel, A ;
Gaudreau, A ;
Côté, M .
IEEE TRANSACTIONS ON POWER DELIVERY, 2004, 19 (04) :1862-1868
[7]  
Kizilcay M., 2003, IEEE BOL POW TECH C
[8]   A new two-terminal numerical algorithm for fault location, distance protection, and arcing fault recognition [J].
Lee, C. J. ;
Park, J. B. ;
Shin, J. R. ;
Radojevie, Z. M. .
IEEE TRANSACTIONS ON POWER SYSTEMS, 2006, 21 (03) :1460-1462
[9]  
Leprettre B., 2001, 6 INT S SIGN PROC AP
[10]  
Livie J., 2007, P 19 INT C EL DISTR, P1