Solar/waste heat driven two-stage adsorption chiller: the prototype

被引:214
作者
Saha, BB [1 ]
Akisawa, A [1 ]
Kashiwagi, T [1 ]
机构
[1] Tokyo Univ Agr & Technol, Dept Mech Syst Engn, Koganei, Tokyo 1848588, Japan
关键词
D O I
10.1016/S0960-1481(00)00107-5
中图分类号
X [环境科学、安全科学];
学科分类号
08 ; 0830 ;
摘要
Nowadays, adsorption heat pumps receive considerable attention as they are energy savers and environmentally benign. In this study silica gel-water is taken as the adsorbent refrigerant pair. To exploit solar/waste heat of temperatures below 70 degreesC, staged regeneration is necessary. A new two-stage non-regenerative adsorption chiller design and experimental prototype is proposed. Experimental temperature profiles of heat transfer fluid inlets and outlets are presented. The two-stage cycle can be operated effectively with 55 degreesC solar/waste heat in combination with a 30 degreesC coolant temperature. In this paper the physical adsorption of silica gel, working principle and features of a two-stage chiller are described. (C) 2000 Elsevier Science Ltd. All rights reserved.
引用
收藏
页码:93 / 101
页数:9
相关论文
共 15 条
[1]  
BEIJER HA, 1994, P INT ABS HEAT PUMP, V31, P457
[2]  
Boelman EC, 1995, ASHRAE TRAN, V101, P358
[3]   Modeling the performance of two-bed, silica gel-water adsorption chillers [J].
Chua, HT ;
Ng, KC ;
Malek, A ;
Kashiwagi, T ;
Akisawa, A ;
Saha, BB .
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 1999, 22 (03) :194-204
[4]   Rapid cycling solar/biomass powered adsorption refrigeration system [J].
Critoph, RE .
RENEWABLE ENERGY, 1999, 16 (1-4) :673-678
[5]  
Critoph RE, 1988, P INT C POMP CHAL CH, P202
[6]  
Dehler F. C., 1940, CHEM METALL ENG, V37, P307
[7]   EXPERIMENTAL-STUDY OF CASCADING ADSORPTION CYCLES [J].
DOUSS, N ;
MEUNIER, F .
CHEMICAL ENGINEERING SCIENCE, 1989, 44 (02) :225-235
[8]  
GUILLEMINOT JJ, 1993, P INT ABSORPTION HEA, V31, P401
[9]  
JONES JA, 1993, ASHRAE TRAN, V99, P54
[10]  
Kashiwagi T.J.A.T, 1997, ASHRAE T, V103, P50