Analysis of Zig-Zag transformer applying in the three-phase four-wire distribution power system

被引:84
作者
Jou, HL [1 ]
Wu, JC
Wu, KD
Chiang, WJ
Chen, YH
机构
[1] Natl Kaohsiung Univ Appl Sci, Dept Elect Engn, Kaohsiung 807, Taiwan
[2] Kun Shan Univ Technol, Dept Elect Engn, Tainan, Taiwan
关键词
neutral current; three-phase four-wire; Zig-Zag;
D O I
10.1109/TPWRD.2005.844281
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
The load unbalance and the nonlinear loads result in a significant neutral current in the three-phase four-wire distribution power system. The Zig-Zag transformer has been proposed to attenuate the neutral current of the three-phase four-wire distribution power system. In this paper, an analysis is carried out and computer simulation is used to evaluate the performance of the Zig-Zag transformer under ideal and nonideal power conditions. The simulation results show that (a) the Zig-Zag transformer can effectively attenuate the neutral current and zero-sequence harmonic currents on the utility side under the balanced utility voltage, (b) the utility side neutral current becomes larger under the unbalanced utility voltage or the distorted utility voltage with zero sequence harmonic components after applying the Zig-Zag transformer, (c) the insertion of an inductor in the utility side of the neutral conductor can alleviate overloading of the neutral current caused by the unbalanced utility voltages and the distorted utility voltages with zero sequence harmonic components.
引用
收藏
页码:1168 / 1173
页数:6
相关论文
共 10 条
[1]  
BIRD BK, 1983, INTRO POWER ELECT
[2]  
CHENG PT, 2001, P IEEE APEC, V2, P1287
[3]  
DAHONO PA, 1997, IEEE P POW CONV C AU, V2, P683
[4]   ANALYSIS AND DESIGN OF A NEW ACTIVE POWER FILTER TO CANCEL NEUTRAL-CURRENT HARMONICS IN 3-PHASE 4-WIRE ELECTRIC DISTRIBUTION-SYSTEMS [J].
ENJETI, PN ;
SHIREEN, W ;
PACKEBUSH, P ;
PITEL, IJ .
IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, 1994, 30 (06) :1565-1572
[5]   Compensation for neutral current harmonics in a three-phase four-wire system by a synchronous machine [J].
Fukami, T ;
Onchi, T ;
Naoe, N ;
Hanaoka, R .
IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, 2002, 38 (05) :1232-1236
[6]  
KHERA PP, 1990, CONFERENCE RECORD OF THE 1990 IEEE INDUSTRY APPLICATIONS SOCIETY ANNUAL MEETINGS, PARTS 1 AND 2, P1092, DOI 10.1109/IAS.1990.152320
[7]   The grounding of power systems above 600 volts: A practical view point [J].
Nelson, JP .
INDUSTRY APPLICATIONS SOCIETY 50TH ANNUAL PETROLEUM AND CHEMICAL INDUSTRY CONFERENCE, 2003, :13-22
[8]  
QUINN CA, 1993, APPL POWER ELECT CO, P841, DOI 10.1109/APEC.1993.290773
[9]  
WADA K, 2002, P IEEE IAS, V1, P64
[10]  
WANG ZJ, 2002, STUDY HARMONICS TAIW