Prediction of thermal comfort, IAQ, and energy consumption in a dense occupancy environment with the under floor air distribution system

被引:48
作者
Fathollahzadeh, Mohammad Hassan [1 ]
Heidarinejad, Ghassem [1 ]
Pasdarshahri, Hadi [1 ]
机构
[1] Tarbiat Modares Univ, Fac Mech Engn, Tehran, Iran
关键词
Under floor air distribution system; Large indoor environment; Return air vent height; Energy consumption; Thermal comfort; SUPPLY DISPLACEMENT VENTILATION; DISTRIBUTION UFAD SYSTEM; OFFICE;
D O I
10.1016/j.buildenv.2015.03.019
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
The objective of this study is to investigate an under floor air distribution (UFAD) system with combined and separate return and exhaust air vents regarding thermal comfort, indoor air quality (IAQ), and energy consumption. This ventilation system is used in a large indoor environment (dense occupancy), and two common types of inlet diffusers (direct and swirl) are used. Computational fluid dynamics (CFD) methods are used to predict thermal comfort conditions of occupants, IAQ and energy consumption in this space. Based on the results, direct inlet diffusers cannot lead to an acceptable temperature gradient in vertical direction in none of the examined return air vent positions, but swirl inlet diffusers can lead to an acceptable one. By precisely considering thermal comfort conditions, and IAQ made by swirl inlet diffusers, opting the upper boundary of the occupied zone (1.7 m) for return air vent position (which is the optimum case study among all the examined case studies) can lead to the best results. Moreover, the optimum return air vent position in this UFAD system can result to 10.5 percent reduction in the amount of energy consumption compared to the mixing ventilation system. (C) 2015 Elsevier Ltd. All rights reserved.
引用
收藏
页码:96 / 104
页数:9
相关论文
共 29 条
[1]   Saving energy by using underfloor-air-distribution (UFAD) system in commercial buildings [J].
Alajmi, Ali ;
El-Amer, Wid .
ENERGY CONVERSION AND MANAGEMENT, 2010, 51 (08) :1637-1642
[2]   Thermal comfort assessment of an office building served by under-floor air distribution (UFAD) system - A case study [J].
Alajmi, Ali F. ;
Baddar, Faisal A. ;
Bourisli, Raed I. .
BUILDING AND ENVIRONMENT, 2015, 85 :153-159
[3]  
[Anonymous], 1994, ISO7730
[4]  
ASHRAE, 2009, ASHRAE HDB FUND
[5]   An experimental study of stratified flow in enclosures [J].
Awad, A. S. ;
Calay, R. K. ;
Badran, O. O. ;
Holdo, A. E. .
APPLIED THERMAL ENGINEERING, 2008, 28 (17-18) :2150-2158
[6]  
Bauman F, 2001, ASHRAE J, V43, P18
[7]  
Bauman F.S., 2003, UNDERFLOOR AIR DISTR
[8]  
Chen GY, 1998, ENERG BUILDINGS, V28, P137
[9]   Experimental and numerical investigations on stratified air distribution systems with special configuration: Thermal comfort and energy saving [J].
Cheng, Yuanda ;
Niu, Jianlei ;
Liu, Xiaoping ;
Gao, Naiping .
ENERGY AND BUILDINGS, 2013, 64 :154-161
[10]   Stratified air distribution systems in a large lecture theatre: A numerical method to optimize thermal comfort and maximize energy saving [J].
Cheng, Yuanda ;
Niu, Jianlei ;
Gao, Naiping .
ENERGY AND BUILDINGS, 2012, 55 :515-525