Analysis of common mode Voltage - "Neutral shift" in medium voltage PWM adjustable speed drive (MV-ASD) systems

被引:89
作者
Rendusara, DA [1 ]
Cengelci, E
Enjeti, PN
Stefanovic, VR
Gray, JW
机构
[1] Texas A&M Univ, Dept Elect Engn, Power Elect & Power Qual Lab, College Stn, TX 77843 USA
[2] Toshiba Int Corp, Ind Div, Houston, TX 77041 USA
关键词
common mode; medium voltage drove;
D O I
10.1109/63.892827
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
In this paper analysis of common mode voltage or "neutral shift" in the new emerging voltage source inverter type medium voltage adjustable speed drive (MV-ASD) systems is presented. Both cascaded multilevel (CML) inverter and 3-level NPC inverter topologies are analyzed. An equivalent circuit model to determine the common mode voltage stress is presented. Analysis and simulation results are discussed and worst case common mode voltage excursion is computed for an example 800 Hp, 4160 V MV-ASD. It is shown that certain system components are excessively stressed and in the MV-ASD system these data are particularly useful in specifying system components and for proper design of the system. Possible effects of common mode voltage and its dv/dt on medium voltage motor bearings are discussed. A new multilevel PWM strategy is introduced which results in zero common-mode voltage. Simulation results are shown to illustrate the effectiveness of these schemes. Finally, experimental results from a 800 hp, 4160 V,MV-ASD system are presented.
引用
收藏
页码:1124 / 1133
页数:10
相关论文
共 17 条
[1]  
Baker R. H., 1981, U.S. Patent, Patent No. [4270,163, 4270163]
[2]   CALCULATION OF NEUTRAL VOLTAGE SHIFT IN LCI DRIVEN INDUCTION-MOTORS [J].
BUSHMAN, RE ;
SALON, SJ ;
HESSE, MH ;
KING, J .
IEEE TRANSACTIONS ON ENERGY CONVERSION, 1991, 6 (03) :507-513
[3]   The effects of PWM voltage source inverters on the mechanical performance of rolling bearings [J].
Busse, DF ;
Erdman, JM ;
Kerkman, RJ ;
Schlegel, DW ;
Skibinski, GL .
IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, 1997, 33 (02) :567-576
[4]   Source of induction motor bearing currents caused by PWM inverters [J].
Chen, S ;
Lipo, TA ;
Fitzgerald, D .
IEEE TRANSACTIONS ON ENERGY CONVERSION, 1996, 11 (01) :25-32
[5]   Bearing currents and shaft voltages of an induction motor under hard- and soft-switching inverter excitation [J].
Chen, ST ;
Lipo, TA .
IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, 1998, 34 (05) :1042-1048
[6]  
*EL POW RES I, 1992, TR101140 EL POW RES
[7]  
Hammond P. W., 1997, U.S. Patent, Patent No. [US005625545A, 005625545]
[8]  
HAMMOND PW, 1995, PETR CHEM IND C 1995, P231
[9]   Medium-voltage adjustable-speed drives - Users' and manufacturers' experiences [J].
Hanna, RA ;
Prabhu, S .
IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, 1997, 33 (06) :1407-1415
[10]  
LATAIRE P, 1998, EPE J, V7