Measurement of synchronous machine parameters using Kalman filter based fuzzy logic estimator

被引:16
作者
Al-Hamadi, H. M. [1 ]
EL-Naggar, K. M. [2 ]
机构
[1] Kuwait Univ, CFW, Dept Informat Sci, Safat 13060, Kuwait
[2] Coll Technol Studies, Dept Elect Engn, Shuwaikh 70654, Kuwait
关键词
Estimation; Kalman filter; Fuzzy logic; Synchronous machine parameters; Short circuit test; ONLINE MEASUREMENTS; IDENTIFICATION; GENERATOR; TESTS;
D O I
10.1016/j.measurement.2010.07.012
中图分类号
T [工业技术];
学科分类号
08 ;
摘要
This paper presents a new Kalman filter/fuzzy logic approach for estimating synchronous machine parameters from short circuit tests. The technique uses on-line noisy measurements of the short circuit current for estimating direct axis reactances, and time constant synchronous machine parameters. The approach is based on expressing short circuit current as a discrete time linear dynamic system model suitable for the Kalman filter to estimate the parameters. Fuzzy rule-based logic is used to tune-up measurement noise levels by adjusting the covariance matrix. The results show a better convergence using fuzzy logic than those solely using the Kalman filter. (C) 2010 Elsevier Ltd. All rights reserved.
引用
收藏
页码:1327 / 1335
页数:9
相关论文
共 17 条
[1]   DETERMINATION OF SYNCHRONOUS MACHINE ELECTRICAL CHARACTERISTICS BY TEST [J].
DEMELLO, FP ;
HANNETT, LN .
IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1983, 102 (12) :3810-3815
[2]  
ELNAGGAR KM, 2002, 2 IASTED INT C POW E, V48
[3]   IDENTIFICATION OF GENERALIZED MODELS OF SYNCHRONOUS MACHINES FROM TIME-DOMAIN TESTS [J].
KAMWA, I ;
VIAROUGE, P ;
DICKINSON, EJ .
IEE PROCEEDINGS-C GENERATION TRANSMISSION AND DISTRIBUTION, 1991, 138 (06) :485-498
[4]  
KAMWA I, 1990, TRANSACTIONS, V5, P401
[5]   Identification of Heffron-Phillips model parameters for synchronous generators using online measurements [J].
Karrari, M ;
Malik, O .
IEE PROCEEDINGS-GENERATION TRANSMISSION AND DISTRIBUTION, 2004, 151 (03) :313-320
[6]   Identification of physical parameters of a synchronous generator from online measurements [J].
Karrari, M ;
Malik, OP .
IEEE TRANSACTIONS ON ENERGY CONVERSION, 2004, 19 (02) :407-415
[7]   Online parameter estimation of round rotor synchronous generators including magnetic saturation [J].
Kyriakides, E ;
Heydt, GT ;
Vittal, V .
IEEE TRANSACTIONS ON ENERGY CONVERSION, 2005, 20 (03) :529-537
[8]  
Kyriakides E., 2004, J ELECT POWER SYSTEM, V2004, P7
[9]  
LEE CC, 1977, POWER, V96, P97
[10]  