摘要
A more realistic theoretical simulation model for a tubular solar adsorption refrigerating system using activated carbon methanol (AC/M) pair has been introduced. The mathematical model represents the heat and mass transfer inside the adsorption bed, the condenser, and the evaporator. The simulation technique takes into account the variations of ambient temperature and solar radiation along the day. Furthermore, the local pressure, and local thermal conductivity variations in space and time inside the tubular reactor are investigated as well. A C++ computer program is written to solve the proposed numerical model using the finite difference method. The developed program covers the operations of all the system components along the cycle time. The performance of the tubular reactor, the condenser, and the evaporator has been discussed. Time allocation chart and switching operations for the solar refrigeration system processes are illustrated as well. The case studied has a 1 m(2) surface area solar flat plate collector integrated with a 20 stainless steel tubes containing the AC/M pair and each tube has a 5 cm outer diameter. In addition, the condenser pressure is set to 54.2 kpa. It has been found that, the solar coefficient of performance and the specific cooling power of the system are 0.211 and 2.326 respectively. In addition, the pressure distribution inside the adsorption bed has been found nearly uniform and varying only with time. Furthermore, the AC/M thermal conductivity is shown to be constant in both space and time. (C) 2010 Elsevier Ltd. All rights reserved.
引用
收藏
页码:530 / 537
页数:8
相关论文
共 44 条
[1]   Mass recovery adsorption refrigeration cycle-improving cooling capacity [J].
Akahira, A ;
Alam, KCA ;
Hamamoto, Y ;
Akisawa, A ;
Kashiwagi, T .
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2004, 27 (03) :225-234
[2]   Numerical study of heat and mass transfer in adsorption porous medium heated by solar energy: Boubnov-Galerkin method [J].
Al Mers, A ;
Mimet, A .
HEAT AND MASS TRANSFER, 2005, 41 (08) :717-723
[3]   A four-bed mass recovery adsorption refrigeration cycle driven by low temperature waste/renewable heat source [J].
Alam, KCA ;
Akahira, A ;
Hamamoto, Y ;
Akisawa, A ;
Kashiwagi, T .
RENEWABLE ENERGY, 2004, 29 (09) :1461-1475
[4]  
[Anonymous], National Climate Data and Information Archive
[5]  
Anyanwu E.E., 2000, ENVIRON PROT ENG, V26, P17
[6]   Review of solid adsorption solar refrigerator I: an overview of the refrigeration cycle [J].
Anyanwu, EE .
ENERGY CONVERSION AND MANAGEMENT, 2003, 44 (02) :301-312
[7]  
BIDYUT BS, 1995, ENERGY, V20, P983
[8]   Modeling of adsorption heat pumps with heat regeneration [J].
Chahbani, MH ;
Labidi, J ;
Paris, J .
APPLIED THERMAL ENGINEERING, 2004, 24 (2-3) :431-447
[9]   Modeling the performance of two-bed, silica gel-water adsorption chillers [J].
Chua, HT ;
Ng, KC ;
Malek, A ;
Kashiwagi, T ;
Akisawa, A ;
Saha, BB .
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 1999, 22 (03) :194-204
[10]   Multi-bed regenerative adsorption chiller - improving the utilization of waste heat and reducing the chilled water outlet temperature fluctuation [J].
Chua, HT ;
Ng, KC ;
Malek, A ;
Kashiwagi, T ;
Akisawa, A ;
Saha, BB .
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2001, 24 (02) :124-136