Comparative measurement of surge arrester residual voltages by D-dot probes and dividers

被引:29
作者
Metwally, I. A. [1 ]
机构
[1] Sultan Qaboos Univ, Coll Engn, Dept Elect & Comp Engn, Muscat 123, Oman
关键词
Arresters; Charge coupled devices; Impulse testing; Pulse generation; Voltage dividers; Voltage measurement; TRANSIENTS; BEHAVIOR;
D O I
10.1016/j.epsr.2011.01.015
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
This paper presents the design and testing of coaxial D-dot probes with three different designs, namely, totally closed, totally open and semi-open designs. The latter design gives a good response and has an easy-access assembly for fixing and replacing the surge arresters (SA) under test. Simultaneous measurements of residual voltage for 9-kV SA are conducted by the designed probes, and resistive and universal dividers (RD and MRCD). The divider compensation principle is also introduced and implemented for both dividers. Both perfectly compensated dividers and the designed D-dot probes have an error of about 2.5% in the SA residual voltage due to the unavoidable resistance of connecting leads. SA residual voltages measured by uncompensated short MCRD divider give good agreement with that measured by the D-dot probe. The former has small inductive overshoot which can be neglected as the residual voltage crests before the discharge current by a few microseconds. (C) 2011 Elsevier B.V. All rights reserved.
引用
收藏
页码:1274 / 1282
页数:9
相关论文
共 32 条
[1]  
Abdel-Salam M., 2000, High-Voltage Engineering: Theory and Practice, V2nd
[2]  
[Anonymous], 2010, IEC Stan- dard 60060-2:2010
[3]  
[Anonymous], 2003, INT C POW SYST TRANS
[4]  
[Anonymous], 2004, 600994 IEC
[5]  
BARGIGIA A, 1987, 5 INT S HIGH VOLT EN
[6]   CHARACTERISTICS OF LIGHTNING SURGES MEASURED AT METAL-OXIDE DISTRIBUTION ARRESTERS [J].
BARKER, PP ;
MANCAO, RT ;
KVALTINE, DJ ;
PARRISH, DE .
IEEE TRANSACTIONS ON POWER DELIVERY, 1993, 8 (01) :301-310
[7]  
BREILMANN W, 1987, 5 INT S HIGH VOLT EN
[8]   Simulation of Metal Oxide Surge Arresters Behavior [J].
Christodoulou, Christos A. ;
Assimakopoulou, Fani A. ;
Gonos, Ioannis F. ;
Stathopulos, Ioannis A. .
2008 IEEE POWER ELECTRONICS SPECIALISTS CONFERENCE, VOLS 1-10, 2008, :1862-1866
[9]  
Creed Frank C., 1989, GENERATION MEASUREME
[10]   THE RESPONSE OF METAL-OXIDE SURGE ARRESTERS TO STEEP FRONTED CURRENT IMPULSES [J].
DANG, C ;
PARNELL, TM ;
PRICE, PJ .
IEEE TRANSACTIONS ON POWER DELIVERY, 1986, 1 (01) :157-163