Power quality impact of a sea located hybrid wind park

被引:30
作者
Thiringer, T [1 ]
Petru, T
Liljegren, C
机构
[1] Chalmers Univ Technol, Dept Elect Power Engn, S-41296 Gothenburg, Sweden
[2] Gotland Energi AB, S-62030 Slite, Sweden
关键词
Flicker contribution - Harmonic current injection - Hybrid wind park - Power quality;
D O I
10.1109/60.921462
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
The power quality impact of a 2.5 MW wind park has been measured and analyzed. The turbines in the park operate at variable speed at low wind speeds and at fixed speed at higher wind speeds. The harmonic current injection is low and the calculated flicker contribution is seldom above 0.25, The wind park also has the potential to maintain the voltage on the supplying grid below a certain limit, in this case 11 kV.