Transient stability of DFIG wind turbines at an external short-circuit fault

被引:127
作者
Sun, T [1 ]
Chen, Z [1 ]
Blaabjerg, F [1 ]
机构
[1] Aalborg Univ, Inst Energy Technol, DK-9220 Aalborg, Denmark
关键词
doubly fed induction generator (DFIG); short-circuit fault; transient stability; voltage recovery; wind turbine;
D O I
10.1002/we.164
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
The fast development of wind power generation brings new requirements for wind turbine integration into the network. After clearance of an external short-circuit fault, grid-connected wind turbines should restore their normal operation without power loss caused by disconnections. This article concentrates on the transient stability of variable speed wind turbines with doubly fed induction generators (DFIGs) at an external short-circuit fault. A simulation model of a MW-level variable speed wind turbine with a DFIG developed in PSCAD/EMTDC is presented and the control and protection schemes are described in detail. The transient process of grid-connected wind turbines with DFIGs at an external short-circuit fault is analysed, and in critical post-fault situations a measure is proposed for the voltage recovery of DFIG wind turbines after fault clearance. Simulation results demonstrate that in uncritical post-fault situations the control schemes are able to restore the wind turbine's normal operation without disconnections. It is also proved that the proposed measure is effective in re-establishing the voltage at the wind turbine terminal in critical post-fault situations. Copyright (c) 2005 John Wiley & Sons, Ltd.
引用
收藏
页码:345 / 360
页数:16
相关论文
共 20 条
  • [1] Akhmatov V., 2001, P EUR WIND EN C COP, P1182
  • [2] [Anonymous], 2000, P WIND POW 21 CENT E
  • [3] [Anonymous], 2003, PSCAD US GUID
  • [4] [Anonymous], 2003, ANAL DYNAMIC BEHAV E
  • [5] Power electronics as efficient interface in dispersed power generation systems
    Blaabjerg, F
    Chen, Z
    Kjaer, SB
    [J]. IEEE TRANSACTIONS ON POWER ELECTRONICS, 2004, 19 (05) : 1184 - 1194
  • [6] BLAABJERG F, 2003, J POWER ELECTRON, V3, P81
  • [7] *ELTRA TRANS SYST, 2000, SPEC CONN WIND FARMS
  • [8] Giroux P, 2001, IEEE IND ELEC, P990, DOI 10.1109/IECON.2001.975905
  • [9] Heier S, 2014, Grid integration of wind energy: onshore and offshore conversion systems
  • [10] Comparison of fixed speed and doubly-fed induction wind turbines during power system disturbances
    Holdsworth, L
    Wu, XG
    Ekanayake, JB
    Jenkins, N
    [J]. IEE PROCEEDINGS-GENERATION TRANSMISSION AND DISTRIBUTION, 2003, 150 (03) : 343 - 352