Thermodynamic assessment of power requirements and impact of different gas-turbine inlet air cooling techniques at two different locations in Oman

被引:69
作者
Dawoud, B
Zurigat, YH
Bortmany, J
机构
[1] RWTH Aachen Univ, Chair Tech Thermodynam, D-52062 Aachen, Germany
[2] Univ Jordan, Dept Mech Engn, Amman, Jordan
关键词
inlet-air cooling; gas-turbine; power boosting;
D O I
10.1016/j.applthermaleng.2004.11.007
中图分类号
O414.1 [热力学];
学科分类号
摘要
Gas-turbine inlet air cooling has been considered for boosting the power output during hot seasons. In this paper, the power requirements of several inlet air cooling techniques for gas-turbine power plants in two locations; namely, Marmul and Fahud, in Oman have been evaluated using typical meteorological year (TMY) data. The considered techniques are evaporative cooling, fogging cooling, absorption cooling using both LiBr-H2O and aqua-ammonia, and vapour-compression cooling systems. For evaporative cooling, an 88% approach to the wet-bulb temperature has been considered, compared with a 98% approach for fogging cooling. A design compressor inlet air temperature of 14 degrees C has been assigned to LiBr-water chilling systems. For both aqua-ammonia absorption and vapour-compression refrigerating systems, a design compressor inlet air temperature of 8 degrees C has been selected to avoid the formation of ice fragments as the air is drawn into the mouth of the compressor. These technologies have been compared with respect to their effectiveness in power boosting of small-size gas-turbine power plants used in two oil fields at Marmul and Fahud in the Sultanate of Oman. Fogging cooling is accompanied with 11.4% more electrical energy in comparison with evaporative cooling in both locations. The LiBr-H2O cooling offers 40% and 55% more energy than fogging cooling at Fahud and Marmul, respectively. Applying aqua-ammonia water and vapour-compression cooling, a further annual energy production enhancement of 39% and 46% is expected in comparison with LiBr-H2O cooling at Fahud and Marmul, respectively. (c) 2004 Elsevier Ltd. All rights reserved.
引用
收藏
页码:1579 / 1598
页数:20
相关论文
共 10 条
[1]  
ALBORTMANY JN, 2002, P ASME TURBO EXPO 20
[2]  
[Anonymous], DEV TYPICAL METEOROL
[4]   Effects of evaporative inlet and aftercooling on the recuperated gas turbine cycle [J].
Bassily, AM .
APPLIED THERMAL ENGINEERING, 2001, 21 (18) :1875-1890
[5]  
Brown D. R., 1997, International Journal of Global Energy Issues, V9, P171
[6]   PERFORMANCE AND ECONOMIC ENHANCEMENT OF COGENERATION GAS-TURBINES THROUGH COMPRESSOR INLET AIR COOLING [J].
DELUCIA, M ;
BRONCONI, R ;
CARNEVALE, E .
JOURNAL OF ENGINEERING FOR GAS TURBINES AND POWER-TRANSACTIONS OF THE ASME, 1994, 116 (02) :360-365
[7]  
KRANEIS W, 2000, INCREASED IMPROTANCE
[8]  
LUCAS K, 2003, THERMODYNAMIK GRUNDG
[9]   INTERNATIONAL EQUATIONS FOR THE SATURATION PROPERTIES OF ORDINARY WATER SUBSTANCE - REVISED ACCORDING TO THE INTERNATIONAL TEMPERATURE SCALE OF 1990 (VOL 16, PG 893, 1987) [J].
WAGNER, W ;
PRUSS, A .
JOURNAL OF PHYSICAL AND CHEMICAL REFERENCE DATA, 1993, 22 (03) :783-787
[10]  
ZURIGAT YH, 2001, THERMAL ENERGY STORA, P259