An Adaptive Synchronous-Reference-Frame Phase-Locked Loop for Power Quality Improvement in a Polluted Utility Grid

被引:247
作者
Gonzalez-Espin, Fran [1 ]
Figueres, Emilio [1 ]
Garcera, Gabriel [1 ]
机构
[1] Univ Politecn Valencia, Dept Ingn Elect, Grp Sistemas Elect Ind, Valencia 46022, Spain
关键词
Adaptive filters; adaptive signal processing; lattice filters; phase-locked loop; power grids; power quality; power system harmonics; three-phase electric power; FREQUENCY-RESPONSE; CONSTRAINED POLES; NOTCH FILTER; PLL; SYNCHRONIZATION; ALGORITHMS; CONVERTERS; TRACKING; SYSTEM; IMPACT;
D O I
10.1109/TIE.2011.2166236
中图分类号
TP [自动化技术、计算机技术];
学科分类号
0812 ;
摘要
The proper operation of grid-connected power electronics converters needs using a synchronization technique to estimate the phase of the grid voltage. The performance of this synchronization technique is related to the quality of the consumed or delivered electric power. The synchronous-reference-frame phase-locked loop (SRF-PLL) has been widely used due to its ease of operation and robust behavior. However, the estimated phase can have a considerable amount of unwanted ripple if the grid voltage disturbances are not properly rejected. The aim of this paper is to propose an adaptive SRF-PLL which strongly rejects these disturbances even if the fundamental frequency of the grid voltage varies. This is accomplished by using several adaptive infinite-impulse-response notch filters, implemented by means of an inherently stable Schur-lattice structure. This structure is perfectly suited to be programmed in fixed-point DSPs (i.e., it has high mapping precision, low roundoff accumulation, and suppression of quantization limit cycle oscillations). The proposed adaptive SRF-PLL has been tested by means of the TI TMS320F2812 DSP. The obtained experimental results show that the proposed synchronization method highly rejects the undesired harmonics even if the fundamental harmonic frequency of a highly polluted grid voltage abruptly varies.
引用
收藏
页码:2718 / 2731
页数:14
相关论文
共 49 条
[1]  
[Anonymous], P 30 ANN IEEE POW EL
[2]  
[Anonymous], 2011, 50160 UNEEN
[3]  
[Anonymous], P 40 NAPS
[4]  
[Anonymous], 2000, 9292000 IEEE
[5]  
[Anonymous], 1995, Adaptive IIR Filtering in Signal Processing and Control
[6]  
[Anonymous], PHOT SPEC C 2000 28
[7]  
[Anonymous], 2007, Digital Signal Processing
[8]  
[Anonymous], RTDX 2 0 REF GUID
[9]   New algorithms for improved adaptive convex combination of LMS transversal filters [J].
Arenas-García, J ;
Gómez-Verdejo, V ;
Figueiras-Vidal, AR .
IEEE TRANSACTIONS ON INSTRUMENTATION AND MEASUREMENT, 2005, 54 (06) :2239-2249
[10]   Control for Grid-Connected and Intentional Islanding Operations of Distributed Power Generation [J].
Balaguer, Irvin J. ;
Lei, Qin ;
Yang, Shuitao ;
Supatti, Uthane ;
Peng, Fang Zheng .
IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, 2011, 58 (01) :147-157