Voltage recovery after unbalanced and balanced voltage dips in three-phase systems

被引:83
作者
Bollen, MHJ [1 ]
机构
[1] Chalmers Univ Technol, Dept Elect Power engn, S-41296 Gothenburg, Sweden
关键词
equipment immunity; power quality; power transmission and distribution; voltage dips (sags);
D O I
10.1109/TPWRD.2003.817725
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
This paper studies the recovery of the voltage after a voltage dip due to a fault in a three-phase system. The instant of voltage recovery corresponds to the instant of fault clearing. For single-phase and phase-to-phase faults, a single point-on-wave of voltage recovery can be defined. For two-phase-to-ground and three-phase faults, the recovery takes place in two or three steps. The voltage recovery is described in a systematic way by using a classification of three-phase unbalanced voltage dips. The voltage recovery needs to be modeled correctly for studies of equipment immunity against voltage dips.