Two-stage distributed generation optimal sizing with clustering-based node selection

被引:61
作者
Rotaru, Florina [2 ]
Chicco, Gianfranco [1 ]
Grigoras, Gheorghe [2 ]
Cortina, Gheorghe [2 ]
机构
[1] Politecn Torino, Dipartimento Ingn Elettr, I-10129 Turin, Italy
[2] Gheorghe Asachi Tech Univ Iasi, Fac Elect Engn, Iasi 700050, Romania
关键词
Distributed generation; Clustering; Optimal sizing; Energy losses; Voltage profile; DISTRIBUTION NETWORKS; DISTRIBUTION-SYSTEMS; DISTRIBUTION FEEDER; OPTIMAL PLACEMENT; DG ALLOCATION; OPTIMIZATION; RELIABILITY; ALGORITHM; LOCATION; CAPACITY;
D O I
10.1016/j.ijepes.2012.02.012
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Nowadays, distributed generation (DG) is playing a significant role in the electrical energy systems. The diffusion of DG in the electrical networks could be beneficial to improve network operation, but excessive amounts of DG in operation could cause violations of the system constraints. This paper presents a new method to obtain the optimal size of DG sources in electrical distribution systems, taking into account the time-dependent evolution of generation and load. This method adopts a procedure composed of two nested calculation stages. The external stage is carried out by selecting a set of candidate nodes through a clustering-based approach based on normalised loss sensitivity factors and normalised node voltages. The internal stage is an exhaustive search driven by the calculation of an objective function with energy losses and voltage profile components, aimed at finding upgraded DG sizes using exhaustive search on a set of available sizes at the candidate nodes. The resulting method avoids the combinatorial explosion of the solutions to be analysed and determines pseudo-optimal DG sizing without violation of any of the system constraints under any operating condition. The proposed method is tested on a 20 kV rural distribution network, showing its effectiveness in obtaining the pseudo-optimal solution with a relatively low computational burden. (C) 2012 Elsevier Ltd. All rights reserved.
引用
收藏
页码:120 / 129
页数:10
相关论文
共 54 条
[1]   Heuristic curve-fitted technique for distributed generation optimisation in radial distribution feeder systems [J].
Abu-Mouti, F. S. ;
El-Hawary, M. E. .
IET GENERATION TRANSMISSION & DISTRIBUTION, 2011, 5 (02) :172-180
[2]   Optimal Distributed Generation Allocation and Sizing in Distribution Systems via Artificial Bee Colony Algorithm [J].
Abu-Mouti, Fahad S. ;
El-Hawary, M. E. .
IEEE TRANSACTIONS ON POWER DELIVERY, 2011, 26 (04) :2090-2101
[3]   An analytical approach for DG allocation in primary distribution network [J].
Acharya, Naresh ;
Mahat, Pukar ;
Mithulananthan, N. .
INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 2006, 28 (10) :669-678
[4]   Distributed generation:: a definition [J].
Ackermann, T ;
Andersson, G ;
Söder, L .
ELECTRIC POWER SYSTEMS RESEARCH, 2001, 57 (03) :195-204
[5]   Distributed energy generation and sustainable development [J].
Alanne, Kari ;
Saari, Arto .
RENEWABLE & SUSTAINABLE ENERGY REVIEWS, 2006, 10 (06) :539-558
[6]   Optimal planning of multiple distributed generation sources in distribution networks: A new approach [J].
AlRashidi, M. R. ;
AlHajri, M. F. .
ENERGY CONVERSION AND MANAGEMENT, 2011, 52 (11) :3301-3308
[7]  
Ameli M. T., 2010, 2010 International Conference on Computer Information Systems and Industrial Management Applications (CISIM 2010), P626, DOI 10.1109/CISIM.2010.5643526
[8]  
[Anonymous], 2005, CLUSTERING TECHNIQUE
[9]   Optimal Renewable Resources Mix for Distribution System Energy Loss Minimization [J].
Atwa, Y. M. ;
El-Saadany, E. F. ;
Salama, M. M. A. ;
Seethapathy, R. .
IEEE TRANSACTIONS ON POWER SYSTEMS, 2010, 25 (01) :360-370
[10]   Reliability based optimum location of distributed generation [J].
Banerjee, Binayak ;
Islam, Syed M. .
INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 2011, 33 (08) :1470-1478