The use of psychrometric charts for the optimisation of a thermal swing desiccant wheel

被引:124
作者
Kodama, A [1 ]
Hirayama, T [1 ]
Goto, M [1 ]
Hirose, T [1 ]
Critoph, RE [1 ]
机构
[1] Kumamoto Univ, Dept Appl Chem & Biochem, Kumamoto 8608555, Japan
关键词
adsorption; dehumidification; desiccant wheel; psychrometric chart; rotary; enthalpy; humidity; air conditioning;
D O I
10.1016/S1359-4311(01)00032-1
中图分类号
O414.1 [热力学];
学科分类号
摘要
An effective prediction is proposed to estimate the optimal rotation speed and performance of a rotary adsorber, in which simultaneous enthalpy and humidity changes are dealt with separately by visualising changes of state of product or exhaust air on a psychrometric chart. Assuming that the adsorbent rotor is completely regenerated to equilibrium with the regeneration air during the corresponding period, the optimal rotation speed corresponds to the region of the short time adsorption in which penetration theory holds and enthalpy exchange between both streams through the adsorbent rotor follows the behaviour of a rotary sensible heat exchanger at lower revolution rates. The change of the product/exhaust air condition with increasing rotational speed is presented as a set of simple equations. Also, by considering the relative humidity of product air and that of regeneration air to be almost the same at a sufficiently high flow rates of regeneration air, an optimal rotation speed and the product air condition are easily found by simple calculation. In comparison with experiments, the proposed method gives a rotational speed near the "optimum" and the humidity and temperature of the product air are predicted almost exactly. (C) 2001 Elsevier Science Ltd. All rights reserved.
引用
收藏
页码:1657 / 1674
页数:18
相关论文
共 33 条
[1]  
[Anonymous], TRANSPORT PHENOMENA
[2]   PREDICTION OF HEAT AND MASS REGENERATOR PERFORMANCE USING NONLINEAR ANALOGY METHOD .1. BASIS [J].
BANKS, PJ .
JOURNAL OF HEAT TRANSFER-TRANSACTIONS OF THE ASME, 1985, 107 (01) :222-229
[3]   PREDICTION OF HEAT AND MASS REGENERATOR PERFORMANCE USING NONLINEAR ANALOGY METHOD .2. COMPARISON OF METHODS [J].
BANKS, PJ .
JOURNAL OF HEAT TRANSFER-TRANSACTIONS OF THE ASME, 1985, 107 (01) :230-238
[4]   AN ANALYTICAL EXAMINATION OF METHODS FOR IMPROVING THE PERFORMANCE OF DESICCANT COOLING SYSTEMS [J].
COLLIER, RK ;
COHEN, BM .
JOURNAL OF SOLAR ENERGY ENGINEERING-TRANSACTIONS OF THE ASME, 1991, 113 (03) :157-163
[5]  
COLLIER RK, 1982, ASME, V104, P28
[6]   COMBINED HEAT AND MASS-TRANSFER IN REGENERATORS WITH HYGROSCOPIC MATERIALS [J].
HOLMBERG, RB .
JOURNAL OF HEAT TRANSFER-TRANSACTIONS OF THE ASME, 1979, 101 (02) :205-210
[7]   An adsorptive desiccant cooling using honeycomb rotor dehumidifier [J].
Jin, WL ;
Kodama, A ;
Goto, M ;
Hirose, T .
JOURNAL OF CHEMICAL ENGINEERING OF JAPAN, 1998, 31 (05) :706-713
[8]   OPEN-CYCLE DESICCANT AIR-CONDITIONING AS AN ALTERNATIVE TO VAPOR COMPRESSION COOLING IN RESIDENTIAL APPLICATIONS [J].
JURINAK, JJ ;
MITCHELL, JW ;
BECKMAN, WA .
JOURNAL OF SOLAR ENERGY ENGINEERING-TRANSACTIONS OF THE ASME, 1984, 106 (03) :252-260
[9]  
JURINAK JJ, 1984, ASME, V106, P369
[10]   HIGH-PERFORMANCE, SOLID DESICCANT, OPEN COOLING CYCLES [J].
KANG, TS ;
MACLAINECROSS, IL .
JOURNAL OF SOLAR ENERGY ENGINEERING-TRANSACTIONS OF THE ASME, 1989, 111 (02) :176-183