Comparison of three single-phase PLL algorithms for UPS applications

被引:358
作者
Santos Filho, Rubens M. [1 ]
Seixas, Paulo F. [2 ]
Cortizo, Porfirio C. [2 ]
Torres, Leonardo A. B. [2 ]
Souza, Andre F. [2 ]
机构
[1] Ctr Fed Educ Tecnol Minas Gerais, Dept Eletron, BR-30480000 Belo Horizonte, MG, Brazil
[2] Univ Fed Minas Gerais, Dept Engn Eletron, BR-31270901 Belo Horizonte, MG, Brazil
关键词
mathematical modeling; phase-locked loops (PLLs); uninterruptible power systems (UPSs);
D O I
10.1109/TIE.2008.924205
中图分类号
TP [自动化技术、计算机技术];
学科分类号
0812 ;
摘要
In this paper, the performance assessment of three software single-phase phase-locked loop (PLL) algorithms is carried out by means of dynamic analysis and experimental results. Several line disturbances such as phase-angle jump, voltage sag, frequency step, and harmonics are generated by a DSP together with a D/A converter and applied to each PLL. The actual minus the estimated phase-angle values are displayed, providing a refined method for performance evaluation and comparison. Guidelines for parameters adjustments are also presented. In addition, practical implementation issues such as computational delay effects, ride-through, and computational load are addressed. The developed models proved to accurately represent the PLLs under real test conditions.
引用
收藏
页码:2923 / 2932
页数:10
相关论文
共 15 条