A design day for building load and energy estimation

被引:29
作者
Hong, TZ [1 ]
Chou, SK [1 ]
Bong, TY [1 ]
机构
[1] Natl Univ Singapore, Dept Mech & Prod Engn, Singapore 119260, Singapore
关键词
D O I
10.1016/S0360-1323(98)00035-3
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
We describe how a design day for building energy performance simulation can be selected from a 'typical meteorological year' of a location. The advantages of the design day weather file are its simplicity and flexibility in use with simulation programs. The design day is selected using a weather parameter comprising the daily average dry bulb temperature and total solar insolation. The selection criterion addresses the balance between the need to minimise the part-load performance of the air-conditioning systems and plants and the number of hours of load not met. To validate the versatility of the design day weather file, we compare simulation results of the peak load and load profile of a building obtained fi om the DOE-2, 1 E code and a specially developed load estimation program, PEAKLOAD. PEAKLOAD is developed using the transfer function method and ASHRAE databases. Comparative results are in good agreement, indicating that a design day thus selected can be used when quick answers are required and simulations using a TMY file cannot be easily done or justified, (C) 1999 Elsevier Science Ltd. All rights reserved.
引用
收藏
页码:469 / 477
页数:9
相关论文
共 10 条
[1]  
*BEST, 1995, US GUID BUILD EN CON
[2]  
*CARR CORP, 1988, HAP VERS 1 1 E20 II
[3]  
CLARKE JA, 1986, ESP BUILD PLANT EN S
[4]   OUTDOOR DESIGN CONDITIONS FOR HVAC SYSTEM-DESIGN AND ENERGY ESTIMATION FOR BUILDINGS IN HONG-KONG [J].
LAM, JC ;
HUI, SCM .
ENERGY AND BUILDINGS, 1995, 22 (01) :25-43
[5]  
MCQUISTON FC, 1992, HETING COOLING LOAD
[6]  
Sowell EF., 1988, ASHRAE T, V94, P716
[7]  
Sowell EF, 1988, ASHRAE T, V94, P754
[8]  
*TRAC INC, 1987, CUST DIR SERV NETW U
[9]  
*US NAT TECHN INF, 1980, DOE 2 MAN VERS 2 1
[10]  
1997, AHSRAE HDB FUNDAMENT