摘要
This paper presents the results of an evaluation of a toxicity mitigation control strategy using the IWA simulation benchmark (Respirometry in control of the activated sludge process: benchmarking control strategies, IWA Scientific and Technical Report #11, IWA, London, England, 2002; The COST simulation benchmark: description and simulator manual, Office for Official Publications of the European Community, Luxembourg, 2001, 154pp). The aim of the proposed strategy is to minimise the impact of a toxic influent shock load on process performance. To do this, the strategy depends on a respiration rate measurement to detect toxic events and uses an equalisation tank to store toxic influent. A defined control algorithm specific for the benchmark plant was developed and controls the reintroduction of the stored influent back into the process stream once the influent is deemed non-toxic. Implemented into the benchmark-defined nitrifying configuration, the evaluation required several alterations to the simulation benchmark including three model changes, the addition of a soluble unbiodegradable toxic state variable and the development of two toxic influent files: The results of the simulations indicate that the impact of the toxicant can be significantly mitigated through the use of off-line storage and reintroduction of suspected influent. (C) 2003 Elsevier Science Ltd. All rights reserved.
引用
收藏
页码:305 / 313
页数:9
相关论文
共 6 条
[1]  
ALEX J, 1999, P EUR CONTR C ECC 99
[2]  
[Anonymous], 2005, RESPIROMETRY CONTROL
[3]  
ASM, 2001, COST SIMULATION BENC, P3
[4]  
HENZE M, 1986, 1 IWA
[5]  
PONS MN, 1999, P ESC 9 9 EUR S COMP
[6]  
SPANJERS H, 1998, 7 IWA