Evaluation of the suitability of a fixed speed wind turbine for large scale wind farms considering the new UK grid code

被引:26
作者
El-Helw, H. M. [1 ]
Tennakoon, Sarath B. [1 ]
机构
[1] Staffordshire Univ, Fac Computing Engn & Technol, Stafford ST4 2DE, England
关键词
wind energy; fixed speed wind turbine; induction generator; grid code; short circuit ratio; STATCOM;
D O I
10.1016/j.renene.2007.08.010
中图分类号
X [环境科学、安全科学];
学科分类号
08 ; 0830 ;
摘要
The analysis of the reactive power management of a wind farm consisting of fixed speed wind turbines is carried out. The rating calculation of the compensator for a fixed speed wind farm is evaluated, and the effect of the network strength on the compensator rating is studied. Also the compatibility of fixed speed wind turbine with the new UK grid code requirements is evaluated by simulation using Matlab/Simulink. The simulation results show that the compensator rating is mainly determined by the need to meet the grid code specifications, rather than the steady state reactive power capability obligation. The main conclusion is that a fixed speed wind farm based on simple induction generators is unable to meet the new grid code requirements, unless the compensator rating is increased substantially. (c) 2007 Elsevier Ltd. All rights reserved.
引用
收藏
页码:1 / 12
页数:12
相关论文
共 13 条
[1]   CAPACITANCE REQUIREMENT FOR ISOLATED SELF-EXCITED INDUCTION GENERATOR [J].
ALJABRI, AK ;
ALOLAH, AI .
IEE PROCEEDINGS-B ELECTRIC POWER APPLICATIONS, 1990, 137 (03) :154-159
[2]  
[Anonymous], NEW WORLD REC WIND P
[3]  
Bhadra S. N., 2005, WIND ELECTRICAL SYST
[4]   CAPACITANCE REQUIREMENTS OF SELF-EXCITED INDUCTION GENERATORS [J].
CHAN, TF .
IEEE TRANSACTIONS ON ENERGY CONVERSION, 1993, 8 (02) :304-311
[5]   Comparison of fixed speed and doubly-fed induction wind turbines during power system disturbances [J].
Holdsworth, L ;
Wu, XG ;
Ekanayake, JB ;
Jenkins, N .
IEE PROCEEDINGS-GENERATION TRANSMISSION AND DISTRIBUTION, 2003, 150 (03) :343-352
[6]  
JAUCH C, 2004, P NORD WIND POW C SW
[7]  
Krause PC, 2002, ANAL ELECT MACHINERY
[8]  
*MARHW INC, 2006, SIMPOWERSYST US GUID, V4
[9]   Wind-turbine fault ride-through enhancement [J].
Mullane, A ;
Lightbody, G ;
Yacamini, R .
IEEE TRANSACTIONS ON POWER SYSTEMS, 2005, 20 (04) :1929-1937
[10]  
ORABI M, 2004, P CAN C EL COMP ENG