Thermoeconomic analysis of an evaporative desiccant air conditioning system

被引:42
作者
Camargo, JR
Ebinuma, CD
Silveira, JL
机构
[1] Univ Taubate, UNITAU, Dept Mech Engn, BR-12060440 Taubate, SP, Brazil
[2] Sao Paulo State Univ, UNESP, Coll Engn, Dept Energy, BR-12516410 Guaratingueta, SP, Brazil
关键词
evaporative cooling; desiccant cooling; exergetic manufacturing cost;
D O I
10.1016/S1359-4311(03)00105-4
中图分类号
O414.1 [热力学];
学科分类号
摘要
In this paper, a thermoeconomic analysis method based on the first and second law of thermodynamics and applied to an evaporative cooling system coupled to an adsorption dehumidifier, is presented. The main objective is the use of a method called exergetic manufacturing cost (EMC) applied to a system that operates in three different conditions to minimize the operation costs. Basic parameters are the RIP ratio (reactivation air/process air) and the reactivation air temperature. Results of this work show that the minimum reactivation temperature and the minimum RIP ratio corresponds to the smaller EMC. This result can be corroborated through an energetic analysis. It is noted that this case is also the one corresponding to smaller energy loss. (C) 2003 Elsevier Science Ltd. All rights reserved.
引用
收藏
页码:1537 / 1549
页数:13
相关论文
共 13 条
[1]  
[Anonymous], 1999, 421 WORLD BANK
[2]  
Boehm RF, 1987, Design Analysis of Thermal Systems
[3]  
CAMARGO JR, 2000, THESIS TAUBATE, P106
[4]  
CAMARO JR, 2001, IMPACTO AQUECIMENTO
[5]  
Harriman L. G., 1990, DEHUMIDIFICATION HDB
[6]   Thermoeconomic analysis of a cogeneration system of a university campus [J].
Luz-Silveira, J ;
Beyene, A ;
Leal, EM ;
Santana, JA ;
Okada, D .
APPLIED THERMAL ENGINEERING, 2002, 22 (13) :1471-1483
[7]  
MUNTERS, 1999, SIST VENT RESFR ATR
[8]  
*NOV TECHN, DES WHEEL SEL PROGR
[9]  
SILVEIRA JL, 1998, UMA CONTRIBUICAO MOD, P60
[10]  
SONNTAG RE, 1993, COMPUTER AIDED THERM, V93