Design and experience with a fuzzy logic controller for Automatic Generation Control (AGC)

被引:77
作者
Chown, GA [1 ]
Hartman, RC
机构
[1] Eskom, Generat Elect Engn Dept, Johannesburg, South Africa
[2] Eskom, Syst Operat Dept, Pretoria, South Africa
关键词
Automatic Generation Control (AGC); frequency control; fuzzy logic; fuzzy control; Area Control Error (ACE); proportional control; derivative control; control pulses; tieline control;
D O I
10.1109/59.709084
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
This paper describes the design, implementation and operational performance of a fuzzy controller as part of the Automatic Generation Control (AGC) system in Eskom's National Control Centre. The fuzzy controller was implemented in the control ACE calculation, which determines the shortfall or surplus generation that has to be corrected. This paper sets out the problems associated with secondary frequency control and AGC. The difficulties associated with optimising the original standard AGC controller, the design. implementation and optimisation of the fuzzy controller and the operational performance of the new controller over two years, are discussed. The fuzzy controller was integrated into the existing off-the shelf AGC system with only a few modifications. The operational performance over two years showed an overall improvement of over 50% in the reduction of control compared to the original AGC controller, and an initial improvement of 20% in the quality of control of the optimised original controller.
引用
收藏
页码:965 / 970
页数:6
相关论文
共 9 条
[1]  
Cox E., 1994, FUZZY SYSTEMS HDB PR
[2]  
DASH PK, 1996, IEE P GENER TRANSM D, V143
[3]  
HARTMAN RC, 1995, DETERMINING AMOUNT C
[4]  
Jaleeli Nasser, 1992, IEEE T POWER SYSTEMS, V7
[5]  
KENNEDY T, 1987, 87SM4773 IEEE
[6]  
LIU K, 1995, IFAC CONTROL POWER P
[7]  
*NERC, NERC OP MAN
[8]  
PROWSE DCH, 1992, IEEE SUMM POW M
[9]  
THOMPSON HH, 1989, IEEE T POWER SYSTEMS, V4