Automatic control strategy for biological nitrogen removal of low C/N wastewater in a sequencing batch reactor

被引:8
作者
Kishida, N
Kim, JH
Chen, M
Tsuneda, S
Sasaki, H
Sudo, R
机构
[1] Waseda Univ, Dept Chem Engn, Shinjuku Ku, Tokyo 1698555, Japan
[2] Ctr Environm Sci, Kisaimachi, Saitama 3470115, Japan
[3] Waseda Univ, Dept Environm Resources Engn, Shinjuku Ku, Tokyo 1698555, Japan
关键词
C/N ratio; external carbon source; oxidation-reduction potential (ORP); pH; real-time control;
D O I
10.2166/wst.2004.0605
中图分类号
X [环境科学、安全科学];
学科分类号
08 ; 0830 ;
摘要
To establish an automatic control system of external carbon addition in biological nitrogen removal, a bench-scale sequencing batch reactor with real-time control strategy was designed in this study. An oxidation-reduction potential (ORP) profile as used for automatic control of external carbon addition. The mean removal efficiency of total organic carbon was over 98%. Complete denitrification in an anoxic phase and complete denitrification and nitrification in anoxic and oxic phases were accomplished, respectively, because the oxic and anoxic periods were also appropriately controlled with ORP and pH profiles, respectively. Mean removal efficiency of total nitrogen was over 95%. When concentration of influent wastewater was changed, volume of additional carbon was automatically changed with the influent, fluctuation, and flexible hydraulic retention time was achieved in this system.
引用
收藏
页码:45 / 50
页数:6
相关论文
共 13 条
[1]   USE OF PH AS CONTROL PARAMETER FOR AEROBIC/ANOXIC SLUDGE-DIGESTION [J].
ALGHUSAIN, I ;
HAO, OJ .
JOURNAL OF ENVIRONMENTAL ENGINEERING-ASCE, 1995, 121 (03) :225-235
[2]  
ALGHUSAIN IA, 1994, WATER SCI TECHNOL, V30, P159
[3]  
*AM PUBL HLTH ASS, 1995, STAND METH EX WAT WA
[4]   The feasible sequential control strategy of treating high strength organic nitrogen wastewater with sequencing batch biofilm reactor [J].
Cho, BC ;
Chang, CN ;
Liaw, SL ;
Huang, PT .
WATER SCIENCE AND TECHNOLOGY, 2001, 43 (03) :115-122
[5]   pH and oxidation-reduction potential control strategy for optimization of nitrogen removal in an alternating aerobic-anoxic system [J].
Kim, H ;
Hao, OJ .
WATER ENVIRONMENT RESEARCH, 2001, 73 (01) :95-102
[6]  
Kishida N, 2003, J BIOSCI BIOENG, V96, P285, DOI 10.1016/S1389-1723(03)80195-0
[7]   OXIDATION-REDUCTION POTENTIAL - A TOOL FOR MONITORING, CONTROL AND OPTIMIZATION OF BIOLOGICAL NUTRIENT REMOVAL SYSTEMS [J].
KOCH, FA ;
OLDHAM, WK .
WATER SCIENCE AND TECHNOLOGY, 1985, 17 (11-1) :259-281
[8]   REDUCING NITROUS-OXIDE GAS EMISSIONS FROM FILL-AND-DRAW TYPE ACTIVATED-SLUDGE PROCESS [J].
OSADA, T ;
KURODA, K ;
YONAGA, M .
WATER RESEARCH, 1995, 29 (06) :1607-1608
[9]   Emission and control of nitrous oxide from a biological wastewater treatment system with intermittent aeration [J].
Park, KY ;
Inamori, Y ;
Mizuochi, M ;
Ahn, KH .
JOURNAL OF BIOSCIENCE AND BIOENGINEERING, 2000, 90 (03) :247-252
[10]   USE OF ORP FOR MONITORING AND CONTROL OF AEROBIC SLUDGE-DIGESTION [J].
PEDDIE, CC ;
MAVINIC, DS ;
JENKINS, CJ .
JOURNAL OF ENVIRONMENTAL ENGINEERING-ASCE, 1990, 116 (03) :461-471