Pumped storage in systems with very high wind penetration

被引:140
作者
Tuohy, A. [1 ]
O'Malley, M. [2 ]
机构
[1] Elect Power Res Inst, Knoxville, TN USA
[2] Univ Coll Dublin, Sch Elect Elect & Mech Engn, Dublin 4, Ireland
关键词
Power system modelling; Wind energy; Large scale energy storage; POWER-SYSTEM; OPTIMIZATION; GENERATION; CAPACITY;
D O I
10.1016/j.enpol.2011.01.026
中图分类号
F [经济];
学科分类号
02 ;
摘要
This paper examines the operation of the Irish power system with very high levels of wind energy, with and without pumped storage. A unit commitment model which accounts for the uncertainty in wind power is used. It is shown that as wind penetration increases, the optimal operation of storage depends on wind output as well as load. The main benefit from storage is shown to be a decrease in wind curtailment. The economics of the system are examined to find the level at which storage justifies its capital costs and inefficiencies. It is shown that the uncertainty of wind makes the option of storage more attractive. The size of the energy store has an impact on results. At lower levels of installed wind (up to approximately 50% of energy from wind in Ireland), the reduction in curtailment is insufficient to justify building storage. At greater levels of wind, storage reduces curtailment sufficiently to justify the additional capital costs. It can be seen that if storage replaces OCGTs in the plant mix instead of CCGTs, then the level at which it justifies itself is lower. Storage increases the level of carbon emissions at wind penetration below 60%. (C) 2011 Elsevier Ltd. All rights reserved.
引用
收藏
页码:1965 / 1974
页数:10
相关论文
共 37 条
[1]  
[Anonymous], 2009, ACC HIGH LEV VAR GEN
[2]  
[Anonymous], VTT WORKING PAPERS
[3]  
[Anonymous], 2008, ALL ISLAND RENEWABLE
[4]  
[Anonymous], GLOB WIND EN OUTL 20
[5]  
[Anonymous], IEEE POW EN SOC GEN
[6]  
[Anonymous], 2010, ALL ISL TSO FAC REN
[7]  
AWERBUCH S, 2006, MITIGATION ADAPTATIO
[8]  
BARTH R, 2006, 9 INT C PROB METH AP
[9]   Optimization of pumped storage capacity in an isolated power system with large renewable penetration [J].
Brown, Paul D. ;
Pecas Lopes, J. A. ;
Matos, Manuel A. .
IEEE TRANSACTIONS ON POWER SYSTEMS, 2008, 23 (02) :523-531
[10]   On the optimization of the daily operation of a wind-hydro power plant [J].
Castronuovo, ED ;
Lopes, JAP .
IEEE TRANSACTIONS ON POWER SYSTEMS, 2004, 19 (03) :1599-1606