Performance of MOV arresters during very close, direct lightning strikes to a power distribution system

被引:13
作者
Fernandez, MI [1 ]
Rambo, KJ [1 ]
Rakov, VA [1 ]
Uman, MA [1 ]
机构
[1] Univ Florida, Dept Elect & Comp Engn, Lighting Res Lab, Gainesville, FL 32611 USA
基金
美国国家航空航天局; 美国国家科学基金会;
关键词
lightning; MOV arresters;
D O I
10.1109/61.754082
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
In 1996, at the International Center for Lightning Research and Testing (ICLRT) at Camp Blanding, Florida, the responses of MOV arresters in an unenergized test distribution system, composed of an overhead line, underground cable, and padmount transformer with a resistive load, were measured during very close, direct lightning strikes to the overhead line. Arresters were installed on the overhead line at two locations 50 m apart (on either side of the strike point) and at the primary of the padmount transformer which was connected to the line via the underground cable. We obtained arrester data for this test configuration from two lightning flashes (containing a total of five strokes) which were artificially initiated from a natural thunderstorm, using the rocket-and-wire technique. We present the simultaneously-recorded arrester discharge current and voltage waveforms from one lightning stroke for one of the two arresters on the line and for the arrester at the transformer primary. Additionally, we estimate the energy absorbed by the arrester on the line as a fUnction of time for the first 4 ms of the lightning event. The records presented are representative of those for all five strokes.
引用
收藏
页码:411 / 418
页数:8
相关论文
共 8 条
[1]   CHARACTERISTICS OF LIGHTNING SURGES MEASURED AT METAL-OXIDE DISTRIBUTION ARRESTERS [J].
BARKER, PP ;
MANCAO, RT ;
KVALTINE, DJ ;
PARRISH, DE .
IEEE TRANSACTIONS ON POWER DELIVERY, 1993, 8 (01) :301-310
[2]   Induced voltage measurements on an experimental distribution line during nearby rocket triggered lightning flashes [J].
Barker, PP ;
Short, TA ;
EybertBerard, AR ;
Berlandis, JP .
IEEE TRANSACTIONS ON POWER DELIVERY, 1996, 11 (02) :980-995
[3]  
FERNANDEZ MI, 1997, THESIS U FLORIDA GAI
[4]   PARAMETERS OF TRIGGERED-LIGHTNING FLASHES IN FLORIDA AND ALABAMA [J].
FISHER, RJ ;
SCHNETZER, GH ;
THOTTAPPILLIL, R ;
RAKOV, VA ;
UMAN, MA ;
GOLDBERG, JD .
JOURNAL OF GEOPHYSICAL RESEARCH-ATMOSPHERES, 1993, 98 (D12) :22887-22902
[5]  
Greenwood A., 1991, ELECT TRANSIENTS POW
[6]  
SCHNEIDER HM, 1979, IEEE PES SUMM M
[7]  
Uman M., 1987, The Lightning Discharge
[8]  
Uman M. A., 1997, Transactions of the Institute of Electrical Engineers of Japan, Part B, V117-B, P446