Comparison of different frequency controllers for a VSC-HVDC supplied system

被引:65
作者
Du, Cuiqing [1 ]
Agneholm, Evert [2 ]
Olsson, Gustaf [2 ,3 ,4 ]
机构
[1] ABB AB, HVDC, S-77180 Ludvika, Sweden
[2] GothiaPower AB, SE-41133 Gothenburg, Sweden
[3] Chalmers Univ Technol, SE-41296 Gothenburg, Sweden
[4] Lund Univ, S-22100 Lund, Sweden
关键词
current limit; frequency controllers; voltage dips; voltage disturbance ride-through capability; voltage source converters-high-voltage direct current (VSC-HVDC);
D O I
10.1109/TPWRD.2008.921130
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
This paper studies three different frequency controllers and their effects on the voltage disturbance ride-through capability of a VSC-HVDC supplied industrial system. The idea of implementing frequency controller is to improve the power quality of industrial plants by slightly decreasing the VSC output voltage frequency since industrial processes are more sensitive to voltage drops than frequency deviations. The first two controllers, frequency controllers I and II, are fixed frequency controllers and the third one, frequency controller III, is a PI frequency controller. In order to compare three different controllers, a system with a simplified VSC-HVDC and different load types is simulated in PSCAD/EMTDC. Simulation results show that with frequency controller III, the VSC-HVDC supplied industrial plant can avoid a voltage collapse by decreasing frequency during or after disturbances. Furthermore, with an increase of the converter current limit, the possibility of mitigating voltage dips increases. For frequency controllers I and II, the extent of the disturbance ride-through capability depends on the current limit of the VSC-UVDC. A higher current limit results in a higher ride-through capability. The effect of the dc capacitor on improving the system voltage disturbance tolerance is also investigated during and after disturbances when the VSC-HVDC uses frequency controller I. The system voltage disturbance ride-through capability increases with an increase of the dc capacitance or the current limit.
引用
收藏
页码:2224 / 2232
页数:9
相关论文
共 33 条
  • [1] ALAKULA M, 2002, POWER ELECT CONTROL
  • [2] [Anonymous], 2003, ELECT POWER SYSTEMS
  • [3] [Anonymous], 1998, POWER SYSTEM DYNAMIC
  • [4] [Anonymous], THESIS LUND I TECHNO
  • [5] AXELSSON U, 1999, P CIRED C NIC FRANC
  • [6] PROPOSED CHAPTER-9 FOR PREDICTING VOLTAGE SAGS (DIPS) IN REVISION TO IEEE STD-493, THE GOLD-BOOK
    BECKER, C
    BRAUN, W
    CARRICK, K
    DILIBERTI, T
    GRIGG, C
    GROESCH, J
    HAZEN, B
    IMEL, T
    KOVAL, D
    MUELLER, D
    STJOHN, T
    CONRAD, LE
    [J]. IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, 1994, 30 (03) : 805 - 821
  • [7] Comparison of theory and experiment on aeroacoustic loads and deflections
    Campos, LMBC
    Bourgine, A
    Bonomi, B
    [J]. JOURNAL OF FLUIDS AND STRUCTURES, 1999, 13 (01) : 3 - 35
  • [8] AUXILIARY POWER CONTROLS ON THE NELSON RIVER HVDC SCHEME
    CHAND, J
    [J]. IEEE TRANSACTIONS ON POWER SYSTEMS, 1992, 7 (01) : 398 - 402
  • [9] Daly J, 2006, PROCEEDINGS OF THE 4TH INTERNATIONAL CONFERENCE ON NANOCHANNELS, MICROCHANNNELS, AND MINICHANNELS, PTS A AND B, P39
  • [10] A voltage and frequency droop control method for parallel inverters
    De Brabandere, K
    Bolsens, B
    van den Keybus, J
    Woyte, A
    Driesen, J
    Belmans, R
    [J]. PESC 04: 2004 IEEE 35TH ANNUAL POWER ELECTRONICS SPECIALISTS CONFERENCE, VOLS 1-6, CONFERENCE PROCEEDINGS, 2004, : 2501 - 2507