A practical approach to HVDC system control for damping subsynchronous oscillation using the novel eigenvalue analysis program

被引:33
作者
Kim, Dong-Joon [1 ]
Nam, Hae-Kon
Moon, Young-Hwan
机构
[1] Korea Electrotechnol Res Inst, Chang Won 641600, South Korea
[2] Chonnam Natl Univ, Dept Elect Engn, Kwangju 500010, South Korea
关键词
damping controller; eigenvalue analysis; high voltage direct current (HVDC) system; subsynchronous oscillation; time domain simulation;
D O I
10.1109/TPWRS.2007.907974
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
This paper presents a practical approach for supplementary control of high voltage direct current (HVDC) system to damp subsynchronous oscillation (SSO) involving HVDC converters and turbine- generator shaft systems. A novel eigenvalue analysis (NEA) program, HVDC system modeling to consider steady-state and dynamic conditions in a combined ac/dc system, and an appropriate control scheme have been utilized. The design method proposed facilitates the design of a subsynchronous oscillation damping controller (SODC) to provide positive damping torque for the dominant torsional mode in combined ac/dc systems. The suggested SODC design method has been applied to an ac/dc system to verify its practicality using the EMTDC simulation program.
引用
收藏
页码:1926 / 1934
页数:9
相关论文
共 19 条
[11]  
Kundur P., 1994, POWER SYSTEM STABILI, V7
[12]   APPLYING POWER SYSTEM STABILIZERS .1. GENERAL CONCEPTS [J].
LARSEN, EV ;
SWANN, DA .
IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1981, 100 (06) :3017-3024
[13]  
LARSEN EV, 1977, P PICA C, P350
[14]  
*MAN HVDC RES CTR, 2002, PSCAD EMTDC VER 3 0
[15]  
PARNIANI M, 1995, P I ELECT ENG GEN TR, V142, P613
[16]  
PIWKO RJ, 1982, EL2708 EPRI
[17]   EFFECT OF HVDC LINE FAULTS ON TRANSIENT TORSIONAL TORQUES OF TURBINE-GENERATOR SHAFTS [J].
SHI, W ;
IRAVANI, MR .
IEEE TRANSACTIONS ON POWER SYSTEMS, 1994, 9 (03) :1457-1464
[18]  
Szechtman M., 1991, Electra, V135, P54
[19]  
TAKASAKI M, 1992, STUDY AC EDC POWER S