Particulate matter intervention study: A causal factor of building-related symptoms in an older building

被引:27
作者
Kemp, PC
Dingle, P
Neumeister, HG
机构
[1] Murdoch Univ, Sch Environm Sci, Div Sci, Murdoch, WA 6150, Australia
[2] Free Univ Berlin, Inst Hyg, D-12203 Berlin, Germany
来源
INDOOR AIR-INTERNATIONAL JOURNAL OF INDOOR AIR QUALITY AND CLIMATE | 1998年 / 8卷 / 03期
关键词
sick building syndrome (SBS); older buildings; respirable suspended particulate matter (RSP); intervention study; indoor surface pollution (ISP); vacuum cleaning;
D O I
10.1111/j.1600-0668.1998.t01-1-00003.x
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
Five floors of a 20-year old 6-story office building were investigated using an integrated step-by-step investigation strategy. This involved a walkthrough inspection, an occupant questionnaire, and targeted environmental monitoring of indoor air quality and comfort parameters. The initial questionnaire survey revealed a high occurrence of building-related symptoms. The walkthrough inspection and environmental monitoring identified deposits of surface dust (indoor surface pollution - ISP) on carpets and hard surfaces, and elevated levels of carbon dioxide and respirable suspended particulate matter (RSP) throughout the building. An intervention study (blinded to the occupants) was targeted at reducing ISP levels by replacing normal carpet cleaning practices with higher performance vacuum cleaners and improved cleaning practices. The intervention reduced ISP levels and significantly lowered RSP concentrations by approx. 80% from initial values and against control floors. A follow-up SBS questionnaire revealed significant reductions in all but two of the symptoms. The most significant reductions occurred with symptoms of eye irritation, throat irritation, dry unproductive cough, and nose irritation. The study showed that in older buildings with poor ventilation, a build-up of ISP, and elevated RSP levels, using higher performance carpet cleaning practices can reduce RSP to acceptable levels and can reduce SBS symptoms.
引用
收藏
页码:153 / 171
页数:19
相关论文
共 28 条
[1]  
ANDERSSON KSG, 1993, MM QUESTIONNAIRES TO
[2]  
[Anonymous], METHODS DETERMINATIO
[3]  
Baechler M.C, 1991, SICK BUILDING SYNDRO
[4]  
Berglund B., 1992, Indoor Air, V2, P2, DOI [10.1111/j.1600-0668.1992.02-21.x, DOI 10.1111/J.1600-0668.1992.02-21.X]
[5]  
DALES R, 1990, P IND AIR 90 OTT CAN, V1, P145
[6]  
DINGLE P, 1995, THESIS MURDOCH U PER
[7]  
Figley D. A., 1993, P IND AIR 93 HELS 6, V6, P267
[8]  
Godish T., 1995, SICK BUILDINGS DEFIN
[9]   DEMONSTRATION OF MICROORGANISMS AND DUST IN SCHOOLS AND OFFICES - AN OBSERVATIONAL STUDY OF NONINDUSTRIAL BUILDINGS [J].
GRAVESEN, S ;
LARSEN, L ;
GYNTELBERG, F ;
SKOV, P .
ALLERGY, 1986, 41 (07) :520-525
[10]  
GRAVESEN S, 1990, P 5 INT C IND AIR QU, V1, P9