A novel experimental investigation of a solar cooling system in Madrid

被引:179
作者
Syed, A
Izquierdo, M
Rodríguez, P
Maidment, G
Missenden, J
Lecuona, A
Tozer, R
机构
[1] CSIC, Inst Ciencias Construcc Eduardo Torroja, Madrid 28033, Spain
[2] Cundall Johnston & Partners LLP Consulting Engine, London EC1A 9RH, England
[3] London S Bank Univ, Fac Engn Sci & Built Environm, London SE1 0AA, England
[4] Waterman Gore Consulting Engineers, London SE1 8ND, England
[5] Univ Carlos III Madrid, Escuela Politecn Super, Madrid 28911, Spain
来源
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID | 2005年 / 28卷 / 06期
关键词
air conditioning; residential building; Spain; experiment; absorption system; water-lithium bromide; solar collector; thermal storage;
D O I
10.1016/j.ijrefrig.2005.01.007
中图分类号
O414.1 [热力学];
学科分类号
摘要
This paper reports novel experimental results derived through field testing of a part load solar energized cooling system for typical Spanish houses in Madrid during the summer period of 2003. Solar hot water was delivered by means of a 49.9 m(2) array of flat-plate collectors to drive a single-effect (LiBr/H2O) absorption chiller of 35 kW nominal cooling capacity. Thermal energy was stored in a 2 m 3 stratified hot water storage tank during hours of bright sunshine. Chilled water produced at the evaporator was supplied to a row of fan coil units and the heat of condensation and absorption was rejected by means of a forced draft cooling tower. Instantaneous, daily and period energy flows and energy balance in the installation is presented. System and absorption machine temperature profiles are given for a clear, hot and dry day's operation. Daily and period system efficiencies are given. Peak insolation of 969 W m(-2) (at 12:30 solar time on 08/08/03) produced 5.13 kW of cooling at a solar to cooling conversion efficiency of 11%. Maximum cooling capacity was 7.5 kW. Cooling was provided for 8.67 h and the chiller required a threshold insolation of 711 W m(-2) for start-up and 373 W m(-2) for shut-down. A minimum hot water inlet temperature to the generator of 65 degrees C was required to commence cold generation, whereas at 81 degrees C, 6.4 kW of cooling (18.3% of nominal capacity) was produced. The absorption refrigeration machine operated within the generation and absorption temperature ranges of 57-67 and 32-36 degrees C, respectively. The measured maximum instantaneous, daily average and period average COP were 0.60 (at maximum capacity), 0.42 and 0.34, respectively. Energy flows in the system are represented on a novel area diagram. The results clearly demonstrate that the technology works best in dry and hot climatic conditions where large daily variations in relative humidity and dry bulb temperature prevail. This case study provides benchmark data for the assessment of other similar prototypes and for the validation of mathematical models. (C) 2005 Elsevier Ltd and IIR. All rights reserved.
引用
收藏
页码:859 / 871
页数:13
相关论文
共 21 条
[1]  
American Society of Heating Refrigerating and Air-conditioning Engineers (ASHRAE), 1988, ASHRAE EQ HDB
[2]  
Chung R., 1963, MECH ENG, V85
[3]  
Duff W. S., 1999, P ASES SOL 99 C AM S, P175
[4]  
Duffie J.A., 2006, SOLAR ENG THERMAL PR, VThird
[5]  
*IEA, 2000, HPPAN244 IEA HEAT PU, P30
[6]  
IZQUIERDO M, 1984, PON POST P 23 RENC I, P427
[7]  
IZQUIERDO M, 1984, MONOGRAFIA, V17, P121
[8]   European research on solar-assisted air conditioning [J].
Lamp, P ;
Ziegler, F .
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 1998, 21 (02) :89-99
[9]   Experimental studies on a solar powered air conditioning system with partitioned hot water storage tank [J].
Li, ZF ;
Sumathy, K .
SOLAR ENERGY, 2001, 71 (05) :285-297
[10]   Assessment of uncertainty in solar collector modeling and testing [J].
Mathioulakis, E ;
Voropoulos, K ;
Belessiotis, V .
SOLAR ENERGY, 1999, 66 (05) :337-347