Effects of adverse weather and aging on power system reliability

被引:45
作者
Bollen, MHJ [1 ]
机构
[1] Chalmers Univ Technol, Dept Elect Power Engn, S-41296 Gothenburg, Sweden
关键词
component aging; power distribution systems; power system reliability; preventive maintenance; weather-related failures;
D O I
10.1109/28.913708
中图分类号
T [工业技术];
学科分类号
08 [工学];
摘要
Most power system reliability studies assume a constant failure rate and an exponentially distributed repair time, For redundant (parallel) components, using the average component failure rates gives erronous results. The effect of time-varying failure rates is discussed for adverse weather and for component aging. A primary-selective supply is used to introduce the phenomena. In particular, adverse weather is shown to significantly affect the interruption frequency. Both adverse weather and component aging require additional data collection efforts. Including component aging also requires a serious modeling effort.
引用
收藏
页码:452 / 457
页数:6
相关论文
共 7 条
[1]
[Anonymous], 4931997 IEEE
[2]
Billinton R., 1984, Reliability Evaluation of Power Systems, DOI DOI 10.1007/978-1-4615-7731-7
[3]
Billinton R., 1994, Reliability assessment of electrical power systems using Monte Carlo methods
[4]
Bollen M. H., 1999, Understanding Power Quality Problemsvoltage Sags and Interruptions
[5]
METHOD FOR RELIABILITY-ANALYSIS OF INDUSTRIAL DISTRIBUTION-SYSTEMS [J].
BOLLEN, MHJ .
IEE PROCEEDINGS-C GENERATION TRANSMISSION AND DISTRIBUTION, 1993, 140 (06) :497-502
[6]
KOVAL DO, 1988, P 15 INTER RAM INT R, P439
[7]
Reliability assessment in electrical power systems: The Weibull-Markov stochastic model [J].
van Casteren, JFL ;
Bollen, MHJ ;
Schmieg, ME .
IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, 2000, 36 (03) :911-915