Parameterization of a synchronous generator to represent a doubly fed induction generator with chopper protection for fault studies

被引:14
作者
Martinez, Jorge [1 ]
Kjaer, Philip C. [1 ]
Rodriguez, Pedro [2 ,3 ]
Teodorescu, Remus [2 ]
机构
[1] VESTAS Wind Syst, Power Plant R&D, Randers, Denmark
[2] Aalborg Univ, Inst Energy Technol, Aalborg, Denmark
[3] Tech Univ Catalonia, Barcelona, Spain
关键词
Wind turbine generator; operational impedances; simulation; doubly fed induction generator; short circuit currents; synchronous generator; WIND TURBINES;
D O I
10.1002/we.406
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
This paper addresses the representation of the wound rotor asynchronous generators by an equivalent synchronous generator, valid for short circuit current calculations. Modern wind power plants are required and designed to ride through faults in the network, subjected to fault clearing. Accurate knowledge of the wind turbine short circuit current contribution is needed for component sizing and protection relay settings during faults within the wind power plant collector system or in the external networks. When studying fault currents and protection settings for wind power installations, the industry standard is to employ software packages where generators are represented by their equivalent synchronous generator operational impedances. Hence, it is of importance to represent non-synchronous wind generators by an equivalent synchronous generator. Copyright (C) 2010 John Wiley & Sons, Ltd.
引用
收藏
页码:107 / 118
页数:12
相关论文
共 9 条
[1]  
Adkins B., 1975, GEN THEORY ALTERNATI
[2]  
BOIDEA I, 1986, ELECT MACHINE DYNAMI
[3]  
Erlich I, 2005, IEEE POWER ENG SOC, P1253
[4]  
KRAUSE, 1994, ANAL ELECT MACHINERY
[5]  
Kundur P., 1993, Power System Stability And Control
[6]   Ridethrough of wind turbines with doubly-fed induction generator during a voltage dip [J].
Morren, J ;
de Haan, SWH .
IEEE TRANSACTIONS ON ENERGY CONVERSION, 2005, 20 (02) :435-441
[7]   Short-circuit current of wind turbines with doubly fed induction generator [J].
Morren, Johan ;
de Haan, Sjoerd W. H. .
IEEE TRANSACTIONS ON ENERGY CONVERSION, 2007, 22 (01) :174-180
[8]   Doubly fed induction generator using back-to-back PWM converters and its application to variable-speed wind-energy generation [J].
Pena, R ;
Clare, JC ;
Asher, GM .
IEE PROCEEDINGS-ELECTRIC POWER APPLICATIONS, 1996, 143 (03) :231-241
[9]  
Tleis N.D., 2008, POWER SYSTEMS MODELI