Coordinated control and operation of DFIG and FSIG based Wind Farms

被引:8
作者
Foster, Sarah [1 ]
Xu, Lie [1 ]
Fox, Brendan [1 ]
机构
[1] Queens Univ Belfast, Sch Elect Elect Engn & Comp Sci, Belfast BT7 1NN, Antrim, North Ireland
来源
2007 IEEE LAUSANNE POWERTECH, VOLS 1-5 | 2007年
关键词
doubly fed induction generator (DFIG); fixed speed induction generator; rotor side converter (RSC) protection; reactive power compensation;
D O I
10.1109/PCT.2007.4538371
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 [动力工程及工程热物理]; 0820 [石油与天然气工程];
摘要
This paper considers a coordinated control strategy for adjacent FSIG and DFIG based wind farms whereby the reactive power output of the DFIG is prioritised over real power after a fault on the network, in order to boost the FSIG terminal voltage and improve its fault ride through capability. The issue of protection for a DFIG based wind turbine during network fault is also considered. It is seen that the large rotor currents can generally be ascribed to the small converter rating. Different protection arrangements for the converter are examined. The simulation results show that the stability margin of a FSIG can be significantly greater when there is extra reactive power compensation available from a DFIG in the vicinity.
引用
收藏
页码:522 / 527
页数:6
相关论文
共 7 条
[1]
Variable-speed wind turbines with doubly-fed induction generators Part IV: Uninterrupted operation features at grid faults with converter control coordination [J].
Akhmatov, Vladislav .
Wind Engineering, 2003, 27 (06) :519-529
[2]
Performance of Doubly Fed Induction Generator (DFIG) During Network Faults [J].
Anaya-Lara, O. ;
Wu, X. ;
Cartwright, P. ;
Ekanayake, J. ;
Jenkins, N. .
WIND ENGINEERING, 2005, 29 (01) :49-66
[3]
[Anonymous], TECHN INT WIND FARMS
[4]
FOSTER S, 2006, P UPEC 2006 SEPT UK
[5]
Comparison of fixed speed and doubly-fed induction wind turbines during power system disturbances [J].
Holdsworth, L ;
Wu, XG ;
Ekanayake, JB ;
Jenkins, N .
IEE PROCEEDINGS-GENERATION TRANSMISSION AND DISTRIBUTION, 2003, 150 (03) :343-352
[6]
Voltage recovery of grid-connected wind turbines with DFIG after a short-circuit fault [J].
Sun, T ;
Chen, Z ;
Blaabjerg, F .
PESC 04: 2004 IEEE 35TH ANNUAL POWER ELECTRONICS SPECIALISTS CONFERENCE, VOLS 1-6, CONFERENCE PROCEEDINGS, 2004, :1991-1997
[7]
THIRINGER T, 2003, IEEE POW ENG SOC GEN, V3