Fault direction estimation in radial distribution system using phase change in sequence current

被引:106
作者
Pradhan, A. K. [1 ]
Routray, A. [1 ]
Gudipalli, S. Madhan [1 ]
机构
[1] Indian Inst Technol, Dept Elect Engn, Kharagpur 721302, W Bengal, India
关键词
digital relay; directional relay; distributed generation; feeder protection; overcurrent relay; phasor estimation;
D O I
10.1109/TPWRD.2007.905340
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 [电气工程]; 0809 [电子科学与技术];
摘要
When a remotely sited wind farm is connected to the utility power system through a distribution line, the overcurrent relay at the common coupling point needs a directional feature. This paper presents a method for estimating the direction of fault in such radial distribution systems using phase change in current. The difference in phase angle between the positive-sequence component of the current during fault and prefault conditions has been found to be a good indicator of the fault direction in a three-phase system. A rule base formed for the purpose decides the location of fault with respect to the relay in a distribution system. Such a strategy reduces the cost of the voltage sensor and/or connection for a protection scheme which is of relevance in emerging distributed-generation systems. The algorithm has been tested through simulation for different radial distribution systems.
引用
收藏
页码:2065 / 2071
页数:7
相关论文
共 17 条
[1]
Bo Z. Q., 1999, U POW ENG C LEIC UK
[2]
BO ZQ, 2000, P IEEE POW ENG SOC W
[3]
A new digital directional transverse differential, current protection technique [J].
Eissa, MM ;
Malik, OP .
IEEE TRANSACTIONS ON POWER DELIVERY, 1996, 11 (03) :1285-1291
[4]
Evaluation of a new current directional protection technique using field data [J].
Eissa, MM .
IEEE TRANSACTIONS ON POWER DELIVERY, 2005, 20 (02) :566-572
[5]
Elmore WA, 2003, Protective Relaying: Theory and Applications
[6]
NEGATIVE-SEQUENCE OVERCURRENT ELEMENT APPLICATION AND COORDINATION IN DISTRIBUTION PROTECTION [J].
ELNEWEIHI, AF ;
SCHWEITZER, EO ;
FELTIS, MW ;
LATHAM, J ;
ENGELHARDT, KH .
IEEE TRANSACTIONS ON POWER DELIVERY, 1993, 8 (03) :915-924
[7]
Eriksen P. B., 2005, IEEE Power & Energy Magazine, V3, P65, DOI 10.1109/MPAE.2005.1524622
[8]
OPTIMAL ESTIMATION OF VOLTAGE PHASORS AND FREQUENCY DEVIATION USING LINEAR AND NON-LINEAR KALMAN FILTERING - THEORY AND LIMITATIONS [J].
GIRGIS, AA ;
HWANG, TLD .
IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1984, 103 (10) :2943-2951
[9]
Coordination of voltage sag and overcurrent protection in DG systems [J].
Gómez, JC ;
Morcos, MM .
IEEE TRANSACTIONS ON POWER DELIVERY, 2005, 20 (01) :214-218
[10]
An adaptive relaying for the protection of a wind farm interconnected with distribution networks [J].
Jang, SI ;
Choi, JH ;
Kim, JW ;
Choi, DM ;
Kim, KH .
2003 IEEE PES TRANSMISSION AND DISTRIBUTION CONFERENCE & EXPOSITION, VOLS 1-3, CONFERENCE PROCEEDINGS: BLAZING TRAILS IN ENERGY DELIVERY AND SERVICES, 2003, :296-302