Model-based fault detection and diagnosis of HVAC systems using support vector machine method

被引:180
作者
Liang, J. [1 ]
Du, R. [1 ]
机构
[1] Chinese Univ Hong Kong, Dept Automat & Comp Aided Engn, Shatin, Hong Kong, Peoples R China
来源
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID | 2007年 / 30卷 / 06期
关键词
air conditioning; process; detection; anomaly; maintenance;
D O I
10.1016/j.ijrefrig.2006.12.012
中图分类号
O414.1 [热力学];
学科分类号
摘要
Preventive maintenance plays a very important role in the modern Heating, Ventilation and Air Conditioning (HVAC) systems for guaranteeing the thermal comfort, energy saving and reliability. Its key is a cost-effective Fault Detection and Diagnosis (FDD) method. To achieve this goal, this paper proposes a new method by combining the model-based FDD method and the Support Vector Machine (SVM) method. A lumped-parameter model of a single zone HVAC system is developed first, and then the characteristics of three major faults, including the recirculation damper stuck, cooling coil fouling/block and supply fan speed decreasing, are investigated by computer simulation. It is found that the supply air temperature, mixed air temperature, outlet water temperature and control signal are sensitive to the faults and can be selected as the fault indicators. Based on the variations of the system states under the normal and faulty conditions of different degrees, the faults can be detected efficiently by using the residual analysis method. Furthermore, a multi-layer SVM classifier is developed, and the diagnosis results show that this classifier is effective with high accuracy. As a result, the presented Model-Based Fault Detection and Diagnosis (MBFDD) method can help to maintain the health of the HVAC systems, reduce energy consumption and maintenance cost. (c) 2007 Elsevier Ltd and IIR. All rights reserved.
引用
收藏
页码:1104 / 1114
页数:11
相关论文
共 33 条
[1]   Nonlinear control of a heating, ventilating, and air conditioning system with thermal load estimation [J].
Argüello-Serrano, B ;
Vélez-Reyes, M .
IEEE TRANSACTIONS ON CONTROL SYSTEMS TECHNOLOGY, 1999, 7 (01) :56-63
[2]   Automated fault detection and diagnostics for vapor compression cooling equipment [J].
Braun, JE .
JOURNAL OF SOLAR ENERGY ENGINEERING-TRANSACTIONS OF THE ASME, 2003, 125 (03) :266-274
[3]  
Chen J., 2012, Robust model-based fault diagnosis for dynamic systems, VVol. 3
[4]   Transient pattern analysis for fault detection and diagnosis of HVAC systems [J].
Cho, SH ;
Yang, HC ;
Zaheer-uddin, M ;
Ahn, BC .
ENERGY CONVERSION AND MANAGEMENT, 2005, 46 (18-19) :3103-3116
[5]  
Cristianini N., 2000, Intelligent Data Analysis: An Introduction
[6]   Fault diagnosis in air-conditioning systems: A multi-step fuzzy model-based approach [J].
Dexter, AL ;
Ngo, D .
HVAC&R RESEARCH, 2001, 7 (01) :83-102
[7]  
Dexter Arthur., 2001, DEMONSTRATING AUTOMA, P34
[8]   Four dimensional holospectrum - A new method for analyzing force distributions [J].
Du, R ;
Chen, YD ;
Chen, YB .
JOURNAL OF MANUFACTURING SCIENCE AND ENGINEERING-TRANSACTIONS OF THE ASME, 1997, 119 (01) :95-104
[9]  
DU R, 2005, MONITORING DIAGNOSIS
[10]  
FEDERSPIEL CC, 1992, THESIS DEP MECH ENG