Water flow demands for firefighting

被引:5
作者
Hadjisophocleous, GV
Richardson, JK
机构
[1] Carleton Univ, Dept Civil & Environm Engn, Ottawa, ON K1S 5B6, Canada
[2] Ken Richardson Fire Technol Inc, Ottawa, ON K1C 2J5, Canada
关键词
fire flow; heat release rate; fire area; water supplies;
D O I
10.1007/s10694-005-1269-6
中图分类号
T [工业技术];
学科分类号
08 ;
摘要
A new method of calculating water flows for firefighting is developed. The method consists of determining fire flows for offensive operations (extinguishing the source) and defensive operations (protecting exposures). Fire flow for offensive operations is based on fire load densities for building occupancies and the area of the fire, which, combined with time to extinguishment, establish the heat release rate. When also combined with the cooling efficiency of water, a fire flow is determined. Fire flow for defensive operations uses the heat release rate and considers the view factors for the exterior walls coupled with unprotected openings in those walls. Total fire flow is the sum of the flows for offensive and defensive operations.
引用
收藏
页码:173 / 191
页数:19