Adsorption cooling system for cold storage using methanol/silicagel

被引:29
作者
Oertel, K [1 ]
Fischer, M [1 ]
机构
[1] DLR, Inst Tech Thermodynam, D-70569 Stuttgart, Germany
关键词
adsorption cooling; silicagel/water; silicagel/methanol; thermodynamic analysis; experiments;
D O I
10.1016/S1359-4311(97)00107-5
中图分类号
O414.1 [热力学];
学科分类号
摘要
For the cold storage of agricultural products at temperatures of 2-4 degrees C in India, a solar-hybrid cooling system has been developed, using solar energy from flat plate collectors and the waste heat of a genset, operated with producer gas. A commercially available low temperature (80-90 degrees C) adsorption cooling system for air-conditioning application had to be modified for operation at cooling temperatures below the freezing point of water. Methanol instead of water was investigated as a refrigerant. Because of the inferior thermodynamic properties of methanol and the lower operation temperature, the efficiency is reduced. Calculations showed that the COP for a commercial adsorption cooling system is about 30% when operating the system with methanol/silicagel at a chilled water temperature of T-0 = - 2 degrees C, a heating water temperature of T-h = 85 degrees C and a condenser temperature of T-c = 30 degrees C. A laboratory test facility with heating and cooling capacities of about 2 kW was set up. By comparative experiments with water and methanol, the calculations could be validated, though the specific power density is only 1/10 of the commercial system. (C) 1998 Elsevier Science Ltd. All rights reserved.
引用
收藏
页码:773 / 786
页数:14
相关论文
共 7 条
[1]  
*GBU MBH, 1996, ADS CHILL TYP NAK 50
[2]  
KHELIFEA N, 1985, THESIS TU MUNCHEN MU
[3]  
MANDE S, 1997, P CLIMA 2000
[4]  
MEUNIER F, 1996, P INT ABS HEAT PUMP, V1, P193
[5]  
OERTEL K, 1996, 1 DLR
[6]   FUNDAMENTAL-STUDY ON SOLAR POWERED ADSORPTION COOLING SYSTEM [J].
SAKODA, A ;
SUZUKI, M .
JOURNAL OF CHEMICAL ENGINEERING OF JAPAN, 1984, 17 (01) :52-57
[7]  
TREFFINGER P, 1997, P VDI GET C, P463