This paper explores the dynamic behaviour of loads and tap changers during the process of voltage collapse in power systems. Using an exponential recovery load model representing the dynamic behaviour of aggregate loads, the mechanism of voltage collapse is illustrated. Dynamic interaction between loads and transformers is investigated. Based on such dynamic considerations, a tap locking strategy is proposed which ensures that voltage collapse does not occur. Investigations focus on determining a critical value of tap position such that locking at a smaller value of tap results in stable behaviour, but locking at a larger value results in voltage collapse.
引用
收藏
页码:81 / 97
页数:17
相关论文
共 16 条
[1]  
[Anonymous], 3818 CIGRE
[2]   STABILITY ANALYSIS OF POWER-SYSTEM LOADS WITH RECOVERY DYNAMICS [J].
HILL, DJ ;
HISKENS, IA ;
POPOVIC, DH .
INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 1994, 16 (04) :277-286
[3]  
HILL DJ, 1993, IEEE T POWER SYST, V8
[4]  
HILL DJ, 1994, P NSF WORKSH BULK 3
[5]  
HISKENS IA, 1994, P NSF WORKSH BULK 3
[6]  
HSKENS IA, 1993, P 11 POW SYST COMP C
[7]  
KARLSSON D, 1994, IEEE T POWER SYST, V9, P157, DOI 10.1109/59.317546
[8]  
LACHS W, 1978, 780572 IEEE A
[9]  
MANSOUR Y, PUBLICATION, V90
[10]  
MEDANIC J, 1987, IEEE T POWER SYST, P873