A comprehensive validation of two airflow models - COMIS and CONTAM

被引:70
作者
Haghighat, F
Megri, AC
机构
[1] Centre for Building Studies, Concordia University, Montreal, Que.
来源
INDOOR AIR-INTERNATIONAL JOURNAL OF INDOOR AIR QUALITY AND CLIMATE | 1996年 / 6卷 / 04期
关键词
air-flow; multizone; validation; modelling; laboratory and field measurements;
D O I
10.1111/j.1600-0668.1996.00007.x
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
Several airflow and contaminant dispersion models have been developed to study air distribution in buildings. This paper reports the results of a comprehensive validation of two models: COMIS and CONTAM. The validation process was carried out at three different levels: inter-program comparison; validation with experimental data which was collected in a controlled environment; and finally, validation with field measurement data. At the inter-program level, the airflow rates and pressure values predicted by COMIS and CONTAM for a four-zone paper building were compared with the airflow rates and pressures predicted by CBSAIR, AIRNET and BUS. The results show good agreement between these software programs. The second level of validation compares the models' predictions with measured data collected in a controlled environment. Fan pressurisation, smoke and tracer gas tests were conducted to estimate the permeability of building envelope components, to locate cracks, and to determine the interzonal airflow rates between rooms. The results confirm that there is good agreement between predictions made by COMIS and CONTAM; there are, however, some differences between these models' predictions and the measured data. The predictions made by these models were also compared with the results of a tracer gas measurement carried out in a residential building. The predicted and measured values were in good agreement. (C) Indoor Air (1996).
引用
收藏
页码:278 / 288
页数:11
相关论文
共 16 条
[1]  
AMARA F, 1993, THESIS INSA LYON
[2]  
Axley J., 1988, 883814 NBSSIR
[3]  
Axley J. W., 1987, 873661 NBSIR
[4]  
Feustel H. E., 1990, FUNDAMENTALS MULTIZO
[5]  
Furbringer J.-M., 1995, EVALUATION COMIS, P1015
[6]  
HAGHIGHAT F, 1991, ENERG BUILDINGS, V1, P147
[7]  
HAGHIGHAT F, 1988, INT J AMBIENT ENERGY, V10, P115
[8]  
Herrlin M. K., 1992, AIR FLOW STUDIES MUL
[9]  
JUSLIN K, 1983, IAEA NPPC SPEC M NUC, P12
[10]  
KLOTE JH, 1981, 802157 NBSIR