Exact Convex Relaxation of Optimal Power Flow in Radial Networks

被引:463
作者
Gan, Lingwen [1 ]
Li, Na [2 ]
Topcu, Ufuk [3 ]
Low, Steven H. [1 ]
机构
[1] CALTECH, Engn & Appl Sci Div, Pasadena, CA 91125 USA
[2] Harvard Univ, Dept Elect Engn, Boston, MA 02138 USA
[3] Univ Penn, Dept Elect & Syst Engn, Philadelphia, PA 19104 USA
关键词
Optimal power flow (OPF); INTERIOR-POINT METHOD;
D O I
10.1109/TAC.2014.2332712
中图分类号
TP [自动化技术、计算机技术];
学科分类号
080201 [机械制造及其自动化];
摘要
The optimal power flow (OPF) problem determines a network operating point that minimizes a certain objective such as generation cost or power loss. It is nonconvex. We prove that a global optimum of OPF can be obtained by solving a second-order cone program, under a mild condition after shrinking the OPF feasible set slightly, for radial power networks. The condition can be checked a priori, and holds for the IEEE 13, 34, 37, 123-bus networks and two real-world networks.
引用