Comparative analysis of expulsion and current-limiting fuse operation in distribution systems for improved power quality and protection

被引:19
作者
Kojovic, LA [1 ]
Hassler, SP
Leix, KL
Williams, CW
Baker, EE
机构
[1] Cooper Power Syst, Thomas A Edison Tech Ctr, Franksville, WI 53126 USA
[2] Florida Power Corp, Distribut Engn Dept, Orlando, FL USA
关键词
fuse; current-limiting fuse; modeling; EMTP; ATP; distribution systems; power quality;
D O I
10.1109/61.686985
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
This paper presents a comparative analysis of the effects of expulsion and current-limiting fuse (CLF) operations in distribution systems on power quality and system protection. This analysis included field tests of both types of fuses on a distribution system in Florida. To further analyze fuse effects on the voltage dip duration and spread of the overvoltages created during the fuse operations throughout the system, computer simulations were also performed. Unique digital fuse models were developed for use with the EMTP/ATP program. This paper shows that CLFs improve power quality by supporting system voltage during faults, reducing the voltage dip duration, and do not affect load operation. Additionally, CLFs reduce the fault let-through I(2)t.
引用
收藏
页码:863 / 869
页数:7
相关论文
共 10 条
[1]  
CROOKS WR, 1980, PROGR CURRENT LIMITI
[2]  
GANALINGAM S, 1980, IEE P C, V127
[3]  
HIROSE A, 1976, INT C EL FUS THEIR A
[4]  
KOJOVIC LA, 1996, UPEC 96 IR
[5]  
KOJOVIC LA, 1996, ELECT TODAY, V8
[6]  
KOJOVIC LA, 1996, IEEE PES WINT M BALT
[7]  
WILKINS R, 1994, 3 INT C POW QUAL END
[8]  
WILKINS R, 1977, 3 INT S SWITCH ARC P, P212
[9]  
WRIGHT A, 1995, ELECT FUSES
[10]  
WRIGHT A, 1976, P IEE, V123