New outdoor heating design data for Turkey

被引:25
作者
Bulut, H
Büyükalaca, O
Yilmaz, T
机构
[1] Cukurova Univ, Dept Mech Engn, TR-01330 Adana, Turkey
[2] Univ Harran, Dept Engn Mech, TR-63300 Sanliurfa, Turkey
关键词
D O I
10.1016/S0360-5442(03)00118-X
中图分类号
O414.1 [热力学];
学科分类号
摘要
In this study, new outdoor design conditions for space heating were determined for 78 locations within Turkey according to the format recommended by the American Society of Heating, Refrigerating and Air-Conditioning Engineers Inc. (ASHRAE). Dry-bulb temperature corresponding to 99%, 99.6% and 97.5% annual cumulative frequency of occurrence, the mean and standard deviation of the annual minimum dry-bulb temperatures were obtained. These calculations used hourly data measured during at least 13 years. The current heating design conditions used in the calculation of space heating load in Turkey were analyzed based on their frequency levels. Comparison of the existing space heating design data with the data obtained in this study revealed that the current space heating design temperatures are generally stringent and provide total protection. (C) 2003 Elsevier Ltd. All rights reserved.
引用
收藏
页码:1133 / 1150
页数:18
相关论文
共 25 条
[1]  
*AM SOC HEAT REFR, ASHRAE HDB 1993 FUND
[2]  
American Society of Heating Refrigerating and Air-Conditioning Engineers, 1997, ASHRAE HDB 1997 FUND
[3]   New outdoor cooling design data for Turkey [J].
Bulut, H ;
Büyükalaca, O ;
Yilmaz, T .
ENERGY, 2002, 27 (10) :923-946
[4]   Bin weather data for Turkey [J].
Bulut, H ;
Büyükalaca, O ;
Yilmaz, T .
APPLIED ENERGY, 2001, 70 (02) :135-155
[5]   Analysis of variable-base heating and cooling degree-days for Turkey [J].
Büyükalaca, O ;
Bulut, H ;
Yilmaz, T .
APPLIED ENERGY, 2001, 69 (04) :269-283
[6]  
ERTAY HS, 1997, P 11 TURK NAT C THER, V1, P159
[7]  
Fanger P.O., 1982, Thermal comfort
[8]  
GULFERI I, 1966, THESIS ISTANBUL TU G
[9]  
HUI CM, 1996, ENERGY PERFORMANCE A
[10]  
KILKIS B, 1991, UTILIZATION NATURAL