Adequacy Evaluation of Distribution System Including Wind/Solar DG During Different Modes of Operation

被引:168
作者
Atwa, Y. M. [1 ]
El-Saadany, E. F. [1 ]
Salama, M. M. A. [1 ]
Seethapathy, R. [1 ]
Assam, M. [2 ]
Conti, S. [2 ]
机构
[1] Univ Waterloo, Dept Elect & Comp Engn, Waterloo, ON N2L 3G1, Canada
[2] Univ Catania, Dept Elect Engn, I-95124 Catania, Italy
关键词
Distributed generation; distribution system adequacy assessment; reliability; solar energy; wind energy; ENERGY-CONVERSION SYSTEMS; WIND ENERGY; POWER-SYSTEMS; RELIABILITY/COST IMPLICATIONS;
D O I
10.1109/TPWRS.2011.2112783
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Keen interest in the development and utilization of renewable distributed generation (DG) has been currently observed worldwide. The reliability impact of this highly variable energy source is an important aspect that needs to be assessed as renewable power penetration becomes increasingly significant. Distribution system adequacy assessment including wind-based and solar DG units during different modes of operation is described in this paper. Monte Carlo simulation (MCS) and analytical technique are used in this work with a novel utilization of the clearness index probability density function (pdf) to model the solar irradiance using MCS. The results show that there is no significant difference between the outcomes of the two proposed techniques; however, MCS requires much longer computational time. The effect of is-landing appears in the improvement of the loss of load expectation (LOLE) and loss of energy expectation (LOEE).
引用
收藏
页码:1945 / 1952
页数:8
相关论文
共 36 条
[1]  
[Anonymous], 1979, IEEE T POWER AP SYST, V98, P2047, DOI 10.1109/TPAS.1979.319398
[2]   Supply Adequacy Assessment of Distribution System Including Wind-Based DG During Different Modes of Operation [J].
Atwa, Y. M. ;
El-Saadany, E. F. ;
Guise, Anne-Claire .
IEEE TRANSACTIONS ON POWER SYSTEMS, 2010, 25 (01) :78-86
[3]   A sequential simulation technique for adequacy evaluation of generating systems including wind energy [J].
Billinton, R ;
Chen, H ;
Ghajar, R .
IEEE TRANSACTIONS ON ENERGY CONVERSION, 1996, 11 (04) :728-734
[4]   Generating capacity adequacy evaluation of small stand-alone power systems containing solar energy [J].
Billinton, R ;
Bagen .
RELIABILITY ENGINEERING & SYSTEM SAFETY, 2006, 91 (04) :438-443
[5]   Maintaining supply reliability of small isolated power systems using renewable energy [J].
Billinton, R ;
Karki, R .
IEE PROCEEDINGS-GENERATION TRANSMISSION AND DISTRIBUTION, 2001, 148 (06) :530-534
[6]   Reliability evaluation of small stand-alone wind energy conversion systems using a time series simulation model [J].
Billinton, R ;
Bagen ;
Cui, Y .
IEE PROCEEDINGS-GENERATION TRANSMISSION AND DISTRIBUTION, 2003, 150 (01) :96-100
[7]   Reliability/cost implications of utilizing photovoltaics in small isolated power systems [J].
Billinton, R ;
Karki, R .
RELIABILITY ENGINEERING & SYSTEM SAFETY, 2003, 79 (01) :11-16
[8]  
Billinton R, 2002, IEEE CCEC 2002: CANADIAN CONFERENCE ON ELECTRCIAL AND COMPUTER ENGINEERING, VOLS 1-3, CONFERENCE PROCEEDINGS, P72, DOI 10.1109/CCECE.2002.1015177
[9]  
BILLINTON R, 1993, IEEE WESCANEX 93 - COMMUNICATIONS, COMPUTERS AND POWER IN THE MODERN ENVIRONMENT : CONFERENCE PROCEEDINGS, P100, DOI 10.1109/WESCAN.1993.270560
[10]  
Billinton R., 2002, CAPACITY EXPANSION S, P27